Word

 

 

Bit

 

Status Familly

 

 

Status description

 

 

 

 

 

 

Status to 0

 

 

Status to 1

 

 

 

 

 

for

 

 

 

 

 

 

 

 

 

 

 

 

hex

 

 

0 - F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BMS design

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC bypass thermal overload (Nota 7)

 

 

No

 

 

yes

 

46

 

6

 

Minor Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Bypass out of tolerance (Nota 7)

 

 

No

 

 

yes

 

46

 

7

 

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC bypass frequency out of tolerance (Nota 7)

 

No

 

 

yes

 

46

 

9

 

Minor Warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC bypass voltage out of tolerance (Nota 7)

 

 

No

 

 

yes

 

46

 

 

A

Minor Warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC bypass switch (Q4S)

 

 

 

 

Open

 

 

Closed

 

46

 

 

E

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Static switch major fault (Nota 7)

 

 

 

 

absent

 

 

present

 

47

 

0

 

Minor Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter desynchronized with AC bypass

 

 

absent

 

 

present

 

47

 

1

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output switch (Q5N)

 

 

 

 

Open

 

 

Closed

 

47

 

 

B

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charger major fault

 

 

 

 

No

 

 

Yes

 

49

 

0

 

Minor Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery charging (Nota 5)

 

 

 

 

No

 

 

Yes

 

49

 

3

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter major fault (Nota 5)

 

 

 

 

No

 

 

Yes

 

 

4C

1

 

Minor Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter overload (Nota 5)

 

 

 

 

No

 

 

Yes

 

 

4C

2

 

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter thermal overload (Nota 5)

 

 

No

 

 

Yes

 

 

4C

3

 

Minor Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter limitation (Nota 5)

 

 

 

 

No

 

 

Yes

 

 

4C

4

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS fuse fault (Nota 5)

 

 

 

 

absent

 

 

Present

 

 

4C

5

 

Minor Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load Short circuit

 

 

 

 

 

 

absent

 

 

Present

 

 

4F

1

 

Minor Fault

Nota 1 :

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for Battery charge it is necessary to set 2 bits, for legacy

JBUS table

 

 

 

 

 

 

 

 

 

 

 

 

 

Nota 3 : switch status equal

1, when closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nota 4 :

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Galaxy

 

 

 

 

 

 

INMC/NMTC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@41 Hex

 

@41 Bin

 

@41 Bit3

 

@41 Bit2

 

@41 Bit1

 

@41 Bit 1, 2 and 3 in Dec

 

 

 

 

Unitary

2

 

0010

 

0

 

0

 

1

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modular

4

 

0100

 

0

 

1

 

0

 

 

 

 

 

2

 

 

 

 

 

 

Parallel

6

 

0110

 

0

 

1

 

1

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SSC

8

 

1000

 

1

 

0

 

0

 

 

 

 

 

4

 

 

 

Nota 5 : This Information is not present with a Static Switch Cabinet unit.

Nota 6 : Device Ventilation Fault is present only in a Static Switch Cabinet 800kVA, this information is not present in a Static Switch Cabinet

1200kVA

Nota 7 : For a configuration with UPS in parallel with SCC unit, the Main 2 data need to read on the card installed in the SSC unit.

Nota 8 : Available with NMC firmware 808 and UPS package AN

Nota 9 : Available with NMC fw 808 and G7000 package AM

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 77/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 77
Contents Page Contents Notification MGE MIB InstallationMGE Galaxy 7000 Network Management card presentation Protection of the computers / servers Connecting the UPS to the Ethernet networkSupervision of the UPSs over the network Direct sending of E-mail Teleservice for NmtcSending text messages SMS Environment Sensor optionHardware characteristics Technical dataConfiguration EMC CompatibilityNetwork AdministrationEnvironment sensor MIB Management Information BaseModbus/Jbus for Inmc BOOTP/DHCP Default parametersMgeups 1UPS/NMTC+ 9 UPS/INMCIndications Installation Network Management Card & Modbus/Jbus InmcUnpacking and check on contents Sensor installation option Installation in the UPSLED ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Nmtc Inmc ConfigurationConfigure IP parameters Your network is equipped with a Dhcp server Your network is not equipped with a Dhcp server Test after configurationOptimising the performance of your browser Supervision and administration by browserUPS UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Click on Event Log in the menu Event logClick on System log. in the menu System logEmail Notification NotificationPage Sender Mail Message SettingsConfiguration Network settings Page System Notified Applications Page Central shutdown configuration TLSRSAWITH512MD5 Access controlTLS Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Set-up of the shutdown parameters Server protectionShutdown criteria managed by the Network Management Card Shutdown duration Shutdown when backup time is less thanGeneral overview TeleserviceTeleservice procedure Page Choice 1 Restart / Reset Configuration via RS232Choice 2 Modify Network settings Choice 2 Network ConfigurationChoice 1 Read Network settings MGE UPS Systems Network Management Card Choice 3 Lost password / Set Login Password to DefaultChoice 3 Set Ethernet speed Choice 4 Return to Default Configuration 10.1.1 RS232 link configuration and connection Modbus/Jbus installation & useInstallation 10.1.2.1 RS485 connection 10.1.2 RS485 link configuration and connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 2 Modify Jbus settings Choice 1 Display Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 6 Display Jbus frames Choice 5 Return to Jbus Default ConfigurationAdditional Web pages Detailled status table Modbus register mapSSC INMC/NMTCMeasurement table Sensor Measurements table Environnement Sensor .3.3.1 Sensor Status tableSensor customisation table RO Global overview Examples of Modbus register mapMain UPS status UPS on AC Normal inputWord + Bit Main UPS status UPS on BatteryLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Modbus Status Address Value Word + Bit Main UPS status Communication lostAppendices Tables of alarms and eventsTable of alarms and UPS events UPS OK Table of system alarms MGE MIB Snmp objectsPage Page MIB Trap Table des TrapsIsxc GlossaryMIB Management Information Base Network Management ProxyNMS Network Management Station Snmp RebootNSM Network Shutdown Module RFC