68K System Monitor
User's Guide | GE Energy Services |
M - Move Memory
Platform
Description
þ CPM þ D20 | þ D20 ME | þ D20/200 | þ D20/200 ME | þ D25 |
D20 Base | D20 Base | CCU Base | CCU Base |
|
Use this command to copy memory from one memory region to a writeable memory region.
It requires three hexadecimal quantities, which define the:
•source address
•destination address, and
•number of bytes to transfer
Syntax | Below is usage and syntax information for this command |
| ||||
|
|
|
|
| ||
|
| Command Format | m from_addr to_addr num_bytes |
| ||
|
|
|
|
|
|
|
|
| Variables | None |
|
|
|
|
|
|
|
|
|
|
|
| Parameters | from_addr | = | start address of the source region in |
|
|
|
|
|
| hexadecimal |
|
|
|
| to_addr | = | start address of the destination in hexadecimal |
|
|
|
| num_bytes | = | size in bytes (octets), hexadecimal, of the |
|
|
|
|
|
| region to move |
|
|
|
|
|
| ||
|
| Example | Type m 200000 200400 200 and press ENTER. |
| ||
|
|
| Results: This copies the RAM memory region 200000 up to |
| ||
|
|
| 200200 to the region 200400 up to 200600. |
| ||
|
|
| The system displays the prompt when it completes |
| ||
|
|
| this instruction. |
| ||
|
|
|
|
| ||
|
| Special | An attempt to move to EPROM or |
| ||
|
| Considerations | result in a bus error. |
| ||
|
|
| You can modify systems with FLASH EPROM such as the |
| ||
|
|
| D25 and CCUME using this command. |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
General |
Full Release | |
|