American Dryer Corp Phase 7.2.2 user manual Fire Suppression System F.S.S. Valve Check

Page 22

FIRE SUPPRESSION SYSTEM (F.S.S.) VALVE CHECK

The operation of the water solenoid valve can be tested to insure that the water supply system and valve are functional. Before attempting a system check, be sure that ALL water supply shutoff valves to the dryer are in the OPEN position, and the dryer must be in the “READY” Mode where no cycle is loaded or in progress.

The procedure is as follows:

1.Press and hold the red “STOP/CLEAR” key (while in “READY” Mode and no cycle is in progress).

2.Press and hold the “A” key.

3.Water valve will open and water will be dispensed into basket (tumbler) area as long as both keys are held.

The Phase 7 non-coin microprocessor controller (computer) will prompt the user to perform a F.S.S. valve check at every 4000 hours to ensure proper functionality. At the 4000 hour mark, the Phase 7 non-coin microprocessor controller (computer) will wait for end of the cycle and then will prompt the user to “PLEASE EMPTY TUMBLER, THEN PRESS THE ‘STOP/CLEAR’AND ‘A’ KEYS TO TEST THE WATER VALVE”. When the “STOP/CLEAR” and “A” keys are pressed, the Phase 7 non-coin microprocessor controller (computer) will activate the F.S.S. water valve for 2-seconds, at which point the Phase 7 non-coin microprocessor controller (computer) will prompt the user with the following message “IF WATER DID NOT TURN ON,

CALL FOR SERVICE. THANK YOU”.

NOTE: The Phase 7 non-coin microprocessor controller (computer) will not let the user continue until the valve test has been completed.

F.S.S. DIAGNOSTICS MESSAGES

In the event that the Phase 7 non-coin microprocessor controller (computer) detects a fault in the F.S.S., the Phase 7 non-coin microprocessor controller (computer) will display the message “F.S.S. DISABLED…READY”. To find out the reason for the F.S.S. disabling, press and hold the red “STOP/CLEAR” and green “START/ENTER” keys. This will cause the Phase 7 non-coin microprocessor controller (computer) to display one (1) of the following diagnostic messages:

OPEN THERMISTOR PROBE – This message indicates that the F.S.S. thermistor probe is either not connected or is damaged. If this condition is detected, the Phase 7 non-coin microprocessor controller (computer) will immediately enter F.S.S. DISABLED Mode.

SHORTED THERMISTOR PROBE – This message indicates that the F.S.S. thermistor probe is damaged or the wiring is shorted. If this condition is detected, the Phase 7 non-coin microprocessor controller (computer) will immediately enter F.S.S. DISABLED Mode.

DISCONNECTED WATER VALVE – This indicates that the water valve is open or that it is not connected to the Phase 7 non-coin microprocessor controller (computer). If this condition is detected, the Phase 7 non-coin microprocessor controller (computer) will continue to monitor the condition for a period of 5 minutes before entering F.S.S. DISABLED Mode. Once the condition is corrected, the Phase 7 non-coin microprocessor controller (computer) will continue to monitor the condition for 1 minute before exiting F.S.S. DISABLED Mode.

20

Image 22
Contents NON-COIN Retain This Manual In a Safe Place For Future Reference Table of Contents Section Phase 7 NON-COIN Auto Cycle Patent no ,827,627 Section Features Keyboard Touch Pad Symbols = STOP/CLEAR key Program Selections Preprogrammed CyclesPage Automatic Drying Cycle Patent no ,827,627 Operations Manually Loaded CyclesTimed Manual Drying Cycle Operation Temperature Conversion Status Cycle in Progress Temperature DisplayLight Emitting Diode L.E.D. DOT Matrix Display Audio Alert on Times 0 to Wrinkle Guard ProgramPreprogrammed Cycle Preview Reversing Option DiagnosticsProgram Locations Page Preprogrammed Locations for Custom Drying Operating Instructions Operating SequencePage Page MAN Operating Notes System Reset Fire Suppression System F.S.S. Theory of OperationFire Suppression System F.S.S. Valve Check Page D. Display Messages E.D. Display Operating StatusProgramming Instructions Introduction to ProgrammingPage Programming Flowcharts START/ENTER STOP/CLEARPhase Menu Programming Procedure Page Auto Reverse Mode On OFF English Selecting Languages0SELECT Language EspanolSelect System Parameters Dryer SetupSelecting a Dryer Model Select ModelSteam NON-REVERSING GAS ReversingGAS REVERSING, Electric REVERSING, Steam REVERSING, GAS NON Electric ReversingSelecting the System Temperature DEG F Enter Lint Cleaning Frequency 1 to 10 HoursDEG C Setting the Lint Cleaning Frequency Enter Audio Alert on Times 0 to Adjusting the Audio Alert On times System Temp Rotation Sensor Rotation Sensor Press Enter to jump directly to the location OFF Board Address 00 to ZZDryer Address To ZZ Auto Cycle Time OUT to 99 Minutes Auto Cycle Time Out System Temp Enter Lint Cleaning Frequency 1 to 10 Hours Enter Audio Alert on Times 0 to Rotation SensorAuto Cycle Time OUT To 99 Minutes Adjusting Reversing Spin Time and Stop Time Enter Spin Time 30 to 120 Seconds Reversing SetupEnter Stop Time 5 to 10 Seconds Press the up arrow key to increment Setup Wrinkle Guard Audio AlertWrinkle Guard Setup Wrinkle Guard Audio AlertSteam Injection Setup Wrinkle Guard Setup Steam Injection Setup Enter 1ST on Time Cycle511 to 000 First time adjustment is Minutes mm Enter 1ST OFF TimeEnter 2ND on Time Enter 3RD on Time Program 0-40 CyclesProgramming a F Cycles or 0 40 Cycles Program System Cycles ParametersSelect Cycle Type Reverse ModeSelect a F KEY AutoOFF Not Available Not AvailableEnter DRY Temp TimeDRY Enter Dryness LevelEnter Stop Time To 10 Seconds DRY or Extra Extra DRY Enter Cycle AdjustmentEnter DRY Time 0 to 99 Minutes Controlled Cool Down Enter Cool Down Time 0 to 99 MinutesEnter Cool Down Temp 70 to 100 ºF Enter Cool DownSteam Injection Cycle Enter 1ST on Time 511 to From Previous Enter 2ND on Time Enter 3RD on Time Restoring Factory Default Settings Enter Password Confirm Defaults Defaults SET Default Settings YESCycle A-F Parameters Programs Preset by the Factory Cycle 0-40 Parameters Programs Preset by the FactoryPreprogrammed Cycles System Parameters Program Locations Fixed ParametersGas Diagnostic L.E.D. Display Fault Messages StandardsPage Page Page S.S. Diagnostic Conditions INPUT/OUTPUT I/O Board L.E.D. Indicators Brhl RED L.E.DKeyboard Touch PAD Layout Customer Custom Parameter Settings Auto Programmed Cycle Page ADC Part No 08/19/08