36Installing the Secure Router 4134 chassis and hardware components
•Ensure you have a Phillips screwdriver #2.
•Ensure the mounting brackets are firmly installed on the chassis.
•Ensure you have appropriate antistatic materials.
•Nortel recommends you have two people to help lift the chassis into the equipment rack and securing it.
•Ensure your installation site meets the physical, electrical, and environmental requirements described in “Environmental requirements” (page 61). Site location is important for the proper operation of the Secure Router 4134. Place the unit in a clean, dry environment with adequate air circulation. Allow 2 to 3 feet (0.61 to 0.91 m) of additional clearance around the Secure Router 4134 for access to the cable connectors on the front and rear panels.
Procedure steps
Step Action
1With two people, lift the chassis into available rack space.
2Ensure that the chassis is level, and align the screw holes on the chassis brackets with those on the equipment rack.
3Insert the mounting screws. Space the screws evenly to hold the chassis in the frame.
Grounding the chassis
You must properly ground the Secure Router 4134 before you place it in service. You can connect your ground wire to the grounding strip of the equipment rack, but you must also ensure that the equipment rack is properly grounded.
For all installations, you must provide proper grounding through a UL listed terminal attached to the grounding location on the front panel of the router. The grounding lug, as well as the screws and washers necessary to attach it to the Secure Router 4134, ship in the container with the Secure Router.
Average time to install the grounding terminal: 1 minute.