disconnecting Pulsar EX
The "manual bypass" switch 28 is used to remove Pulsar EX for maintenance purposes or standard exchange, while guaranteeing continuity of power supply to your loads.
Operating mode:
cswitch the "manual bypass" 28 from the "NORMAL" position to the intermediate position (see figure 9);
ccheck that, in this position, the "automatic bypass" has been put into operation: indicator light 1f is flashing;
cif the indicator light 1f is still on, the transfer to the "automatic bypass" has not taken place (power voltage or frequency not within the operating range). In this case do not switch to the "BYPASS" and call our
cmove the "manual bypass" switch 28 from the intermediate to the
| … | 1a to 1c off | |
|
| ||
| … | ! |
|
| … | - + |
|
| … | 1d | flashing/operation on |
| "manual bypass" | ||
|
| ||
|
|
| |
% | … | - + 1e off/power on | |
|
1f flashing
intermittent beeps
c shut down Pulsar EX, by releasing the |
"ON/OFF" button 3 ; |
c open the battery circuit breaker 7 on |
"manual bypass" switch 28
NORMAL 

BY-PASS
"NORMAL" position
NORMAL |
intermediate position
%
… … … …
…
!
-+
-
+
1a to 1d n/a
1e off/power on
flashing/load in
1f "automatic bypass"
intermittent beeps
Pulsar EX, and the battery circuit breaker |
32 on the Pulsar EXB battery extension |
module, if it is fitted; |
c disconnect the cable 26 of the connector |
12 of Pulsar EX; |
c unscrew the "manual bypass" module 25 |
or 31 (screw 24 ) and remove it from |
Pulsar EX. |
Your loads are supplied directly by the AC |
power via the "manual bypass" module and |
Pulsar EX is powered down. |
You may now change the UPS, replacing it |
with another UPS of the same type, without |
interrupting your load. In this case do not |
forget to unplug and store the "automatic |
bypass" cartridge 21 .
NORMAL 

BY-PASS
Figure 9
MGE UPS SYSTEMS | Pulsar EX : 51032306XT/BB | 37 |