APC 9000 installation manual Layout for a single-unit UPS with one battery cubicle Rear

Page 12

Installation

Layout for a single-unit UPS with one battery cubicle

rear

>25

cubicle width W

50

cubicle width W

 

(see table)

(see table)

 

 

 

 

 

battery cubicle

 

rectifier-inverter cubicle

80

 

 

 

 

 

 

 

spacing uprights

> 1000

front

 

 

 

 

 

 

 

 

cutouts necessary for

 

 

cable entry from underneath

 

 

a false floor:

 

 

 

200 mm x (W – 160 mm)

 

can equal 0

800

location of trench under cubicles (if applicable)

Fig. 6

Layout for a single-unit UPS with several battery cubicles

rear

battery cubicle 1

battery cubicle 2 containing batteryrectifier-inverter cubicle circuit breaker QF1

front

Fig. 7

on the floor under the cubicles, in the free space equal to the height of the feet. In this case the cables should be run side by side to avoid blocking the flow of air for ventilation. The cables exit from the rear or sides of the cubicles; connection via the top

the Static Switch, filter and auxiliary cubicles are designed for connection via the bottom or top,

for the rectifier-inverter cubicles, a special 400 mm wide connection duct must be added to the right of the cubicle to allow connection via the top.

Layout for an installation with two parallel UPSs and a centralised SSC

rear

 

 

 

 

battery

 

auxiliaries

 

 

 

rect./inv.

 

 

 

 

 

cubicle1

 

 

 

 

 

 

 

cubicle(s) 2

 

(if applicable)

 

 

 

cubicle 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

front

 

 

 

 

 

 

 

 

auxiliaries

rect./inv.

battery

static switch

cubicle 2

cubicle 2

cubicle(s) 1

cubicle

(if applicable)

 

 

 

 

 

 

Fig. 8

34006451EN/AC - Page 12

Image 12
Contents Installation manual Mgetm GalaxyTM34006451EN/AC Contents Characteristics Characteristics common to all cubiclesStatic Switch Cubicle Characteristics of rectifier-inverter cubiclesCharacteristics of Static Switch Cubicles Rectifier-inverter cubicleElectrical parameters for selecting protective devices Electrical parameters for MainsElectrical parameters for Mains 2 415 Rated Mains 1 current InverterElectrical parameters for determining cable cross-sections Parameters for single-unit UPS cablesInstallation with parallel frequency converters Installation with parallel UPSs with a centralised SSCNF C 15-100 authorizes a maximum of 4 cables per phase Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Handing Positioning the cubiclesSide clearances provided by the spacing uprights Rear FrontFloor loads figure Cubicle layout on false floor or normal floor figures 6, 7Cubicle footpads Rear Connection via the bottomLayout for a single-unit UPS with one battery cubicle Rear Power circuit wiring diagrams Diagram for a frequency converter with batteriesSpecial case Diagram for a frequency converter without batteries Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Cubicle mounting and connection Mounting of the left and right cubiclesInternal connections between cubicles XMGD05XFGD06 Connection of power circuits GeneralLeft cubicle of single-unit or parallel UPS with SSC Cross-section AARight cubicle of single-unit UPS XR1 XR8XR9 XR2 XR5 XR3 XR6 XR4 XR7Right cubicle of a parallel UPS with SSC Front RearXR2 XR5 XR3 XR6 XR4 XR7Connection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Connection to battery circuit breaker QF1 Emergency shutdownConnections between Apoz boards Connections between rectifier-inverter cubiclesXM XM XM XM Connections between Misi boards modular UPSs MisiUPS Misi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connection of the battery Temperature Monitor optional ConnectionsXR2 XR1 Temperature Monitor installation in a battery room Temperature Monitor baseDimensions of the Temperature Monitor 75 x 75 x 21 mm Final installation steps Connection of the LED remote indications unitMains 2 line protection Rated inverter output kVA Maximum permissible currentCubicle mounting Left cubicleQ4S XF1-XF2 XM1-XM2Right cubicle of a 2000 kVA Static Switch Front viewLeft cubicle of a 2000 kVA Static Switch FrontRear Front view 120 to 1200 kVA Static Switch Cubicles Details of earthing connections in the various cubiclesRectifier-inverter cubicle Inverter InputKVA Static Switch Cubicles Tele-Monitor unitComz 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC