3. Appendix (to be carried out by qualified personnel only)
3.1 Mains 2 line protection
The rating of the mains 2 line upstream protection
–to protect the static switch thyristors with respect to maximum permissible currents. Refer to the table opposite for a 400 V mains 2 voltage;
–to ensure discrimination with respect to the UPS output fuses (refer to fuse
rated inverter output (kVA)
maximum permissible current
800
19 In for 20 ms
900
19 In for 20 ms
t(s) |
|
|
|
104 |
|
|
|
103 |
|
|
|
102 |
|
|
|
101 |
|
|
|
1 |
|
|
|
|
|
| |
|
|
| |
|
|
| |
104 | 105 | I(A) | |
103 |