Installation
Example of an installation comprising three modular UPSs with an external maintenance bypass
External |
|
|
| External maintenance bypass cubicle |
|
| ||||
|
|
|
|
|
|
|
|
|
| |
maintenance |
|
|
|
|
|
|
|
|
|
|
bypass line |
|
|
|
|
| Q3BP |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| modular UPS cubicle 1 |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| earth |
|
mains 2 |
| Q4S | static |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |||
|
|
| switch |
|
|
|
|
|
| |
mains 1 | Q1 | rectifier | inverter 1 |
| Q5N |
|
| |||
|
|
|
| |||||||
|
| charger |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| frames interconnection for earthing |
|
| ||
earth | battery cubicle | QF1 | + | - | + | - | other battery | earth |
| |
beside rectifier- |
|
|
|
|
| cubicles (if |
| |||
| inverter cubicle 1 |
|
|
|
|
| applicable) |
|
| |
| modular UPS cubicle 2 |
|
|
| frames interconnection for earthing |
| ||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| earth |
|
mains 2 |
| Q4S | static |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |||
|
|
| switch |
|
|
|
|
|
| |
mains 1 | Q1 | rectifier |
|
|
|
|
| Q5N | Q5N | load |
|
|
|
|
|
| |||||
| inverter 2 |
|
| |||||||
|
| charger |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| frames interconnection for earthing |
|
| ||
earth | battery cubicle | QF1 | + | - | + | - | other battery | earth |
| |
beside rectifier- |
|
|
|
|
| cubicles (if |
| |||
| inverter cubicle 2 |
|
|
|
|
| applicable) |
|
| |
|
|
|
|
|
| frames interconnection for earthing |
| |||
| modular UPS cubicle 3 |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| earth |
|
mains 2 |
| Q4S | static |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |||
|
|
| switch |
|
|
|
|
|
| |
mains 1 | Q1 | rectifier |
|
|
|
|
| Q5N |
|
|
| inverter 3 |
|
|
| ||||||
|
| charger |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| frames interconnection for earthing |
|
| ||
earth | battery cubicle | QF1 | + | - | + | - | other battery | earth |
| |
beside rectifier- | cubicles (if |
| ||||||||
| inverter cubicle 3 |
|
|
|
|
| applicable) |
|
|
Fig. 15
Important. The power cables between each UPS and the upstream protection devices must be the same length. The same holds for the power cables between each UPS cubicle and the external maintenance bypass.