APC 9000 Temperature Monitor installation in a battery room, Temperature Monitor base

Page 29

Installation

Connection of the battery "Temperature Monitor" (for a parallel UPS with batteries in the same room)

battery "Temperature Monitor"

BC+

XR2

XR1

12

(unit shown open)

shielded cable (2 twisted

BC– telephone pairs)

+12

remote relay board connector XR4 on rectifier-inverter cubicle 1:

1

 

 

2

 

 

3

BC

temperature

4

BC +

signal

5

12V

power supply

6

+12V

 

7earth

8NC

9earth

10

11

12

remote relay board connector XR4 on next rectifier-inverter cubicle:

shielded cable (1 or 2 twisted telephone pairs)

 

BC

 

3

temperature

4

BC +

signal

5

 

 

6

 

 

7 earth

8 NC

remote relay board connector XR4 on nth rectifier-inverter cubicle:

1

 

 

2

 

 

3

BC

temperature

4

BC +

signal

5

 

 

6

 

 

7earth

8

9earth

10

11

12

Fig. 24

"Temperature Monitor" installation in a battery room

The "Temperature Monitor" should be secured against a wall or any vertical support:

choose a location near the batteries and away from draughts which adversely affect the accuracy of temperature measurements;

position the unit correctly ("on" light in the top left hand corner and cable fed through from the right-hand side);

use the holes provided in the base plate to screw the unit to the vertical support (see figure 25);

unless the connecting cable runs on the surface, break the knock-out in the unit base plate provided for cable entry;

secure the cable by suitable means so that it does not pull on the unit.

"Temperature Monitor" base

board

oblong holes

for fastening screws

oblong holes

for fastening screws

knock-out for lateral cable entry

dimensions of the "Temperature Monitor": 75 x 75 x 21 mm

Fig. 25

34006451EN/AC - Page 29

Image 29
Contents Mgetm GalaxyTM Installation manual34006451EN/AC Contents Characteristics common to all cubicles CharacteristicsCharacteristics of rectifier-inverter cubicles Static Switch CubicleCharacteristics of Static Switch Cubicles Rectifier-inverter cubicleElectrical parameters for Mains Electrical parameters for selecting protective devicesElectrical parameters for Mains 2 415 Rated Mains 1 current InverterParameters for single-unit UPS cables Electrical parameters for determining cable cross-sectionsNF C 15-100 authorizes a maximum of 4 cables per phase Installation with parallel frequency convertersInstallation with parallel UPSs with a centralised SSC Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Positioning the cubicles HandingSide clearances provided by the spacing uprights Rear FrontCubicle layout on false floor or normal floor figures 6, 7 Floor loads figureCubicle footpads Rear Connection via the bottomLayout for a single-unit UPS with one battery cubicle Rear Special case Power circuit wiring diagramsDiagram for a frequency converter with batteries Example of a 2 parallel UPS rectifier-inverters with SSC Diagram for a frequency converter without batteriesModular UPS cubicle External maintenance bypass cubicle Mounting of the left and right cubicles Cubicle mounting and connectionXFGD06 Internal connections between cubiclesXMGD05 General Connection of power circuitsLeft cubicle of single-unit or parallel UPS with SSC Cross-section AAXR1 XR8 Right cubicle of single-unit UPSXR9 XR2 XR5 XR3 XR6 XR4 XR7Front Rear Right cubicle of a parallel UPS with SSCXR2 XR5 XR3 XR6 XR4 XR7XR1 XR2 XR3 XR4 Connection of auxiliary circuits on the remote relay boardEmergency shutdown Connection to battery circuit breaker QF1Connections between Apoz boards Connections between rectifier-inverter cubiclesXM XM XM XM UPS Connections between Misi boards modular UPSsMisi Misi XR8 XR9 XR5 XR6 XR7 Acpz board of the Static Switch CubicleXR2 XR1 Connection of the battery Temperature Monitor optionalConnections Dimensions of the Temperature Monitor 75 x 75 x 21 mm Temperature Monitor installation in a battery roomTemperature Monitor base Connection of the LED remote indications unit Final installation stepsRated inverter output kVA Maximum permissible current Mains 2 line protectionLeft cubicle Cubicle mountingQ4S XF1-XF2 XM1-XM2Front view Right cubicle of a 2000 kVA Static SwitchRear Front view Left cubicle of a 2000 kVA Static SwitchFront Details of earthing connections in the various cubicles 120 to 1200 kVA Static Switch CubiclesRectifier-inverter cubicle Inverter InputComz KVA Static Switch CubiclesTele-Monitor unit 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC