APC 9000 Handing, Positioning the cubicles, Side clearances provided by the spacing uprights Rear

Page 10

2.Installation (to be carried out by qualified personnel only)

2.1 Handing

Unpacked cubicles may be moved using a forklift from the front or from the back. Distances must not exceed a few meters.

2.2Positioning the cubicles

prior to moving the cubicles to their final position, remove the packing material and withdraw the base panels from the space on the side created by the spacing uprights. The panels will be installed at the end of the installation procedure;

spacing uprights on the sides of the cubicles create a 50 mm clearance when cubicles are positioned next to each other, enabling users to open the doors (see figure 4). If a cubicle is installed next to a wall, leave additional space so that the cubicle is 50 mm from the wall;

when the spacing uprights are not required (cubicles are not positioned next to a wall or another cubicle), they may be removed:

loosen the four screws securing the upright,

lift the upright and pull it free,

replace the long gold-coloured screws with the black screws supplied in a bag attached to the cable terminals in the cubicle;

adjust the height of the feet until the first cubicle is perfectly vertical; adjust the feet of the subsequent cubicles so that the all the doors are perfectly aligned.

Side clearances provided by the spacing uprights

rear

50

50

cubicle 1

cubicle 2

front

spacing uprights of cubicle 1

spacing uprights of cubicle 2

Fig. 4

34006451EN/AC - Page 10

Image 10
Contents Installation manual Mgetm GalaxyTM34006451EN/AC Contents Characteristics Characteristics common to all cubiclesCharacteristics of Static Switch Cubicles Static Switch CubicleCharacteristics of rectifier-inverter cubicles Rectifier-inverter cubicleElectrical parameters for Mains 2 415 Electrical parameters for selecting protective devicesElectrical parameters for Mains Rated Mains 1 current InverterElectrical parameters for determining cable cross-sections Parameters for single-unit UPS cablesInstallation with parallel UPSs with a centralised SSC Installation with parallel frequency convertersNF C 15-100 authorizes a maximum of 4 cables per phase Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Side clearances provided by the spacing uprights Rear HandingPositioning the cubicles FrontCubicle footpads Rear Floor loads figureCubicle layout on false floor or normal floor figures 6, 7 Connection via the bottomLayout for a single-unit UPS with one battery cubicle Rear Diagram for a frequency converter with batteries Power circuit wiring diagramsSpecial case Diagram for a frequency converter without batteries Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Cubicle mounting and connection Mounting of the left and right cubiclesXMGD05 Internal connections between cubiclesXFGD06 Left cubicle of single-unit or parallel UPS with SSC Connection of power circuitsGeneral Cross-section AAXR9 Right cubicle of single-unit UPSXR1 XR8 XR2 XR5 XR3 XR6 XR4 XR7XR2 XR5 Right cubicle of a parallel UPS with SSCFront Rear XR3 XR6 XR4 XR7Connection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Connections between Apoz boards Connection to battery circuit breaker QF1Emergency shutdown Connections between rectifier-inverter cubiclesXM XM XM XM Misi Connections between Misi boards modular UPSsUPS Misi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connections Connection of the battery Temperature Monitor optionalXR2 XR1 Temperature Monitor base Temperature Monitor installation in a battery roomDimensions of the Temperature Monitor 75 x 75 x 21 mm Final installation steps Connection of the LED remote indications unitMains 2 line protection Rated inverter output kVA Maximum permissible currentQ4S Cubicle mountingLeft cubicle XF1-XF2 XM1-XM2Right cubicle of a 2000 kVA Static Switch Front viewFront Left cubicle of a 2000 kVA Static SwitchRear Front view Rectifier-inverter cubicle 120 to 1200 kVA Static Switch CubiclesDetails of earthing connections in the various cubicles Inverter InputTele-Monitor unit KVA Static Switch CubiclesComz 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC