APC 9000 installation manual Characteristics common to all cubicles

Page 4

1. Characteristics

1.1 Characteristics common to all cubicles

MGETM GalaxyTM 9000 UPS: example of a rectifier-inverter cubicle

H

L

P

After moving them to their installation location on their pallets, MGETM GalaxyTM 9000 cubicles can be moved short distances using a forklift or pallet-mover when the front, rear and side base panels are not mounted. The forks can be inserted from all four sides into 100 mm ±10 mm high openings;

the unadjusted cubicle height (H) is 1900/2000 mm; after lifting the cubicle, the height can be adjusted ±10 mm by screwing in or out the four feet;

the bearing surface corresponds to the area of the four cylindrical foot pads (60 mm diameter) positioned in each corner of the cubicle;

the cubicle depth (D) is 840 mm (800 mm without doors and panels);

operating temperature range for rectifier-inverter, frequency converter or Static Switch Cubicles: 0 °C to 35 °C at rated output (40 °C for a maximum of 8 hours) and 30 °C maximum for overload conditions. Operation outside the specified temperature range will reduce service life; relative humidity: 95 % maximum;

maximum operating altitude without derating: 1000 m;

connection via the bottom for rectifier-inverter cubicles, or via the top with the addtion of an optional duct that can be installed on the right side of the cubicle. The auxiliary and Static Switch Cubicles are designed for connections via the top

or bottom.

the connection cables may be run in three ways: in a trench running under the cubicles,

under a false floor,

on the floor under the cubicles, in the free space equal to the height of the feet; in this case the cables should be run side by side to avoid blocking the flow of air for ventilation.

the intercubicle connection cables are not supplied (except for the wires for auxiliary interconnections);

normally the cubicles do not have to be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts;

the cubicle doors are secured by Ronis locks (key 405).

34006451EN/AC - Page 4

Image 4
Contents Installation manual Mgetm GalaxyTM34006451EN/AC Contents Characteristics Characteristics common to all cubiclesStatic Switch Cubicle Characteristics of rectifier-inverter cubiclesCharacteristics of Static Switch Cubicles Rectifier-inverter cubicleElectrical parameters for selecting protective devices Electrical parameters for MainsElectrical parameters for Mains 2 415 Rated Mains 1 current InverterElectrical parameters for determining cable cross-sections Parameters for single-unit UPS cablesInstallation with parallel UPSs with a centralised SSC Installation with parallel frequency convertersNF C 15-100 authorizes a maximum of 4 cables per phase Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Handing Positioning the cubiclesSide clearances provided by the spacing uprights Rear FrontFloor loads figure Cubicle layout on false floor or normal floor figures 6, 7Cubicle footpads Rear Connection via the bottomLayout for a single-unit UPS with one battery cubicle Rear Diagram for a frequency converter with batteries Power circuit wiring diagramsSpecial case Diagram for a frequency converter without batteries Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Cubicle mounting and connection Mounting of the left and right cubiclesXMGD05 Internal connections between cubiclesXFGD06 Connection of power circuits GeneralLeft cubicle of single-unit or parallel UPS with SSC Cross-section AARight cubicle of single-unit UPS XR1 XR8XR9 XR2 XR5 XR3 XR6 XR4 XR7Right cubicle of a parallel UPS with SSC Front RearXR2 XR5 XR3 XR6 XR4 XR7Connection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Connection to battery circuit breaker QF1 Emergency shutdownConnections between Apoz boards Connections between rectifier-inverter cubiclesXM XM XM XM Misi Connections between Misi boards modular UPSsUPS Misi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connections Connection of the battery Temperature Monitor optionalXR2 XR1 Temperature Monitor base Temperature Monitor installation in a battery roomDimensions of the Temperature Monitor 75 x 75 x 21 mm Final installation steps Connection of the LED remote indications unitMains 2 line protection Rated inverter output kVA Maximum permissible currentCubicle mounting Left cubicleQ4S XF1-XF2 XM1-XM2Right cubicle of a 2000 kVA Static Switch Front viewFront Left cubicle of a 2000 kVA Static SwitchRear Front view 120 to 1200 kVA Static Switch Cubicles Details of earthing connections in the various cubiclesRectifier-inverter cubicle Inverter InputTele-Monitor unit KVA Static Switch CubiclesComz 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC