APC 9000 Connection of the battery Temperature Monitor optional, Connections, XR2 XR1

Page 28

Installation

2.12 Connection of the battery "Temperature Monitor" (optional)

Connections

This unit must be connected to connector XR4 of the remote relay board of the rectifier-inverter cubicles (see the location of the remote relay board in the figures of the "power circuit connection" section).

use a shielded cable made up of 2 twisted telephone pairs with a conductor cross-section of at least

0.1 mm2 and up to 100 m in length;

do not forget to connect the cable shield to ground pin 7 of connector XR4;

in the case of a parallel UPS configuration, the connections between cubicles may be made by means of a shielded cable made up of 1 or 2 twisted telephone pairs. In this case, the total length of all the connecting cables should not exceed 100 m;

a "Temperature Monitor" can only be connected to several rectifier-inverter cubicles when the batteries of these cubicles are located in the same room at the same ambient temperature.

Connection of the battery "Temperature Monitor" (for a single-unit UPS)

battery "Temperature Monitor"

BC+

XR2

XR1

12

(unit shown open)

BC–

+12

shielded cable (2 twisted telephone pairs)

remote relay board connector XR4:

1

 

 

 

2

 

 

 

3

BC

temperature

4

BC +

signal

5

12V

power supply

6

+12V

 

7

 

 

earth

 

 

8

 

 

 

9earth

10

11

12

Fig. 23

34006451EN/AC - Page 28

Image 28
Contents Installation manual Mgetm GalaxyTM34006451EN/AC Contents Characteristics Characteristics common to all cubiclesStatic Switch Cubicle Characteristics of rectifier-inverter cubiclesCharacteristics of Static Switch Cubicles Rectifier-inverter cubicleElectrical parameters for selecting protective devices Electrical parameters for MainsElectrical parameters for Mains 2 415 Rated Mains 1 current InverterElectrical parameters for determining cable cross-sections Parameters for single-unit UPS cablesInstallation with parallel UPSs with a centralised SSC Installation with parallel frequency convertersNF C 15-100 authorizes a maximum of 4 cables per phase Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Handing Positioning the cubiclesSide clearances provided by the spacing uprights Rear FrontFloor loads figure Cubicle layout on false floor or normal floor figures 6, 7Cubicle footpads Rear Connection via the bottomLayout for a single-unit UPS with one battery cubicle Rear Diagram for a frequency converter with batteries Power circuit wiring diagramsSpecial case Diagram for a frequency converter without batteries Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Cubicle mounting and connection Mounting of the left and right cubiclesXMGD05 Internal connections between cubiclesXFGD06 Connection of power circuits GeneralLeft cubicle of single-unit or parallel UPS with SSC Cross-section AARight cubicle of single-unit UPS XR1 XR8XR9 XR2 XR5 XR3 XR6 XR4 XR7Right cubicle of a parallel UPS with SSC Front RearXR2 XR5 XR3 XR6 XR4 XR7Connection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Connection to battery circuit breaker QF1 Emergency shutdownConnections between Apoz boards Connections between rectifier-inverter cubiclesXM XM XM XM Misi Connections between Misi boards modular UPSsUPS Misi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connections Connection of the battery Temperature Monitor optionalXR2 XR1 Temperature Monitor base Temperature Monitor installation in a battery roomDimensions of the Temperature Monitor 75 x 75 x 21 mm Final installation steps Connection of the LED remote indications unitMains 2 line protection Rated inverter output kVA Maximum permissible currentCubicle mounting Left cubicleQ4S XF1-XF2 XM1-XM2Right cubicle of a 2000 kVA Static Switch Front viewFront Left cubicle of a 2000 kVA Static SwitchRear Front view 120 to 1200 kVA Static Switch Cubicles Details of earthing connections in the various cubiclesRectifier-inverter cubicle Inverter InputTele-Monitor unit KVA Static Switch CubiclesComz 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC