APC 9000 installation manual Connection to battery circuit breaker QF1, Emergency shutdown

Page 23

Installation

Connection to battery circuit breaker QF1

Connect the cable from connector XR3 (pins 7 to 12) of the rectifier-inverter cubicle remote relay board to connector XR1 of the battery cubicle containing battery circuit breaker QF1.

Emergency shutdown

The UPS emergency shutdown function is generally wired to a "mushroom-head" type emergency off button.

Important:

In the case of a complex installation with a number of units, there should only be one emergency shutdown pushbutton and this pushbutton must interrupt all the active conductors of all the units.

For the same reason, it is essential for the pushbutton to open the upstream mains 1, mains 2, and external maintenance bypass line protective circuit breakers.

Each type of unit (UPS and Static Switch Cubicle) must have an independent, volt-free contact connected to the emergency shutdown pushbutton. This pushbutton must therefore have as many contacts as there are units in the installation, as well as the contact or contacts required to open the upstream mains 1 and 2 protective circuit breakers. The emergency shutdown pushbutton turns off the rectifier-chargers and inverters and opens the battery circuit breakers. The emergency shutdown signal will be cleared when the emergency shutdown pushbutton contact has been reset.

The emergency shutdown pushbutton should not be connected to the Static Switch Cubicle since the pushbutton opens the circuit breaker protecting the upstream circuit (mains 2) and the Static Switch Cubicle is therefore no longer powered (invert- ers off and mains 2 down).

2.9Connections between cubicles (modular UPSs or parallel UPSs with SSC)

On modular UPSs, interconnections are made on the APOZ (figure 17) and MISI (figures 19 to 21) boards in the UPS cubicles (see the layout of the boards in the figures in the previous section).

For parallel UPSs with a centralised SSC, interconnections are made on the APOZ boards in the UPS cubicles (figure 17) and the ACPZ boards (see the layout of the boards in the figures in the previous section) in the SSC (figure 18).

Connections between APOZ boards

these connections are made using the ribbon cables supplied;

the purpose of the connection is to make a loop: connector XM137 of the APOZ board of one UPS being connected to connector XM136 of the APOZ board of the next UPS and so on until the first board is returned to.

Important:

Outside the cubicles, group the APOZ inter-board and ACPZ or MISI inter-board connections with the inter-cubicle auxiliary connections, and separate this assembly from the power cables.

Connections between rectifier-inverter cubicles

APOZ board rectifier-inverter 1

XM137

XM136

APOZ board rectifier-inverter 2

XM137

ribbon cables supplied

 

XM136

 

APOZ board rectifier-inverter 3

XM137

XM136

Fig. 17

34006451EN/AC - Page 23

Image 23
Contents Mgetm GalaxyTM Installation manual34006451EN/AC Contents Characteristics common to all cubicles CharacteristicsRectifier-inverter cubicle Static Switch CubicleCharacteristics of rectifier-inverter cubicles Characteristics of Static Switch CubiclesRated Mains 1 current Inverter Electrical parameters for selecting protective devicesElectrical parameters for Mains Electrical parameters for Mains 2 415Parameters for single-unit UPS cables Electrical parameters for determining cable cross-sectionsNF C 15-100 authorizes a maximum of 4 cables per phase Installation with parallel frequency convertersInstallation with parallel UPSs with a centralised SSC Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Front HandingPositioning the cubicles Side clearances provided by the spacing uprights RearConnection via the bottom Floor loads figureCubicle layout on false floor or normal floor figures 6, 7 Cubicle footpads RearLayout for a single-unit UPS with one battery cubicle Rear Special case Power circuit wiring diagramsDiagram for a frequency converter with batteries Example of a 2 parallel UPS rectifier-inverters with SSC Diagram for a frequency converter without batteriesModular UPS cubicle External maintenance bypass cubicle Mounting of the left and right cubicles Cubicle mounting and connectionXFGD06 Internal connections between cubiclesXMGD05 Cross-section AA Connection of power circuitsGeneral Left cubicle of single-unit or parallel UPS with SSCXR2 XR5 XR3 XR6 XR4 XR7 Right cubicle of single-unit UPSXR1 XR8 XR9XR3 XR6 XR4 XR7 Right cubicle of a parallel UPS with SSCFront Rear XR2 XR5XR1 XR2 XR3 XR4 Connection of auxiliary circuits on the remote relay boardConnections between rectifier-inverter cubicles Connection to battery circuit breaker QF1Emergency shutdown Connections between Apoz boardsXM XM XM XM UPS Connections between Misi boards modular UPSsMisi Misi XR8 XR9 XR5 XR6 XR7 Acpz board of the Static Switch CubicleXR2 XR1 Connection of the battery Temperature Monitor optionalConnections Dimensions of the Temperature Monitor 75 x 75 x 21 mm Temperature Monitor installation in a battery roomTemperature Monitor base Connection of the LED remote indications unit Final installation stepsRated inverter output kVA Maximum permissible current Mains 2 line protectionXF1-XF2 XM1-XM2 Cubicle mountingLeft cubicle Q4SFront view Right cubicle of a 2000 kVA Static SwitchRear Front view Left cubicle of a 2000 kVA Static SwitchFront Inverter Input 120 to 1200 kVA Static Switch CubiclesDetails of earthing connections in the various cubicles Rectifier-inverter cubicleComz KVA Static Switch CubiclesTele-Monitor unit 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC