APC 9000 installation manual Acpz board of the Static Switch Cubicle, XR8 XR9 XR5 XR6 XR7

Page 27

Installation

2.11 Connection of "Media Contacts 15" additional auxiliary circuits

(figure 22)

The additional auxiliary circuits of the rectifier-inverter and Static Switch Cubicles are connected to additional remote relay board by means of the 4 connectors (see location of this board in the figures of the "connection of power circuits" section).

recommended cable cross-section: 1 mm2;

the male connectors that fit the female connectors on the board (XR5 to XR9) are supplied;

the contacts are volt-free and are shown in the diagram under the following conditions: UPS on, contact at rest;

contact breaking capacity: 250 V, 5 A.

Note:

In a parallel-connected UPS installation the "load" and "mains 2" signals are provided by the Static Switch Cubicle.

ACPZ board of the Static Switch Cubicle

additional remote relay board

connector XR5 (option)

connector XR6 (option)

connector XR7 (option)

connector XR8 (option)

connector XR9 (option)

1

 

10

1

10

 

1

12

1

12

1

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XR8

 

 

 

XR9

 

XR5

XR6

 

 

 

XR7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) for:

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

overload (2)

 

 

 

 

 

single-unit UPS cubicle,

 

 

3

 

 

 

 

 

 

 

 

 

 

 

modular UPS cubicle,

 

 

4

 

 

 

 

overload (2)

 

 

 

 

 

parallel UPS cubicle with SSC.

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

(2) for:

 

 

 

 

 

7

 

 

 

 

inverter function fault (1)

 

 

 

 

single-unit UPS cubicle,

 

 

8

 

 

 

 

 

 

 

 

modular UPS cubicle,

 

 

9

 

 

 

 

 

 

 

 

 

 

 

parallel UPS cubicle with SSC,

 

 

10

 

 

 

 

inverter function fault (1)

 

 

 

 

Static Switch cubicle.

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

(3) for:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

single-unit UPS cubicle,

 

 

1

 

 

 

 

 

 

 

 

 

 

 

modular UPS cubicle,

 

 

2

 

 

 

 

rectifier-charger operating (1)

 

 

 

 

 

 

 

 

 

 

Static Switch cubicle.

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

(4) in modular UPSs, these functions are

 

 

5

 

 

 

 

rectifier-charger operating (1)

 

 

 

 

 

 

 

 

 

 

available via the "auxiliary information" contact

 

 

6

 

 

 

 

 

 

 

output signals:

 

 

 

 

 

 

 

 

 

(connector XR9, terminals 7-8).

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rectifier-charger function fault (1)

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

(5) for:

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

single-unit UPS cubicle,

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static Switch cubicle.

 

 

11

 

 

 

 

rectifier-charger function fault (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

transfer to Mains 2 inhibited (3)

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

transfer to Mains 2 inhibited (3)

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

transfer function fault (2)

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

transfer function fault (2)

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

transfer to Mains 2 inhibited (4) (5)

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

transfer to Mains 2 with interruption inhibited (4) (5)

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

desynchronization with Mains 2 (3)

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

battery charge current limiting (1)

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

gradual rectifier-charger shutdown (1)

 

input signals:

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

current limiting on generator power (1)

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

remote inverter on (1)

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

remote inverter off (1)

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

auxiliary signal (2)

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 22

34006451EN/AC - Page 27

Image 27
Contents Mgetm GalaxyTM Installation manual34006451EN/AC Contents Characteristics common to all cubicles CharacteristicsRectifier-inverter cubicle Static Switch CubicleCharacteristics of rectifier-inverter cubicles Characteristics of Static Switch CubiclesRated Mains 1 current Inverter Electrical parameters for selecting protective devicesElectrical parameters for Mains Electrical parameters for Mains 2 415Parameters for single-unit UPS cables Electrical parameters for determining cable cross-sectionsInstallation with parallel frequency converters Installation with parallel UPSs with a centralised SSCNF C 15-100 authorizes a maximum of 4 cables per phase Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Front HandingPositioning the cubicles Side clearances provided by the spacing uprights RearConnection via the bottom Floor loads figureCubicle layout on false floor or normal floor figures 6, 7 Cubicle footpads RearLayout for a single-unit UPS with one battery cubicle Rear Power circuit wiring diagrams Diagram for a frequency converter with batteriesSpecial case Example of a 2 parallel UPS rectifier-inverters with SSC Diagram for a frequency converter without batteriesModular UPS cubicle External maintenance bypass cubicle Mounting of the left and right cubicles Cubicle mounting and connectionInternal connections between cubicles XMGD05XFGD06 Cross-section AA Connection of power circuitsGeneral Left cubicle of single-unit or parallel UPS with SSCXR2 XR5 XR3 XR6 XR4 XR7 Right cubicle of single-unit UPSXR1 XR8 XR9XR3 XR6 XR4 XR7 Right cubicle of a parallel UPS with SSCFront Rear XR2 XR5XR1 XR2 XR3 XR4 Connection of auxiliary circuits on the remote relay boardConnections between rectifier-inverter cubicles Connection to battery circuit breaker QF1Emergency shutdown Connections between Apoz boards XM XM XM XM Connections between Misi boards modular UPSs MisiUPS Misi XR8 XR9 XR5 XR6 XR7 Acpz board of the Static Switch CubicleConnection of the battery Temperature Monitor optional ConnectionsXR2 XR1 Temperature Monitor installation in a battery room Temperature Monitor baseDimensions of the Temperature Monitor 75 x 75 x 21 mm Connection of the LED remote indications unit Final installation stepsRated inverter output kVA Maximum permissible current Mains 2 line protectionXF1-XF2 XM1-XM2 Cubicle mountingLeft cubicle Q4SFront view Right cubicle of a 2000 kVA Static SwitchLeft cubicle of a 2000 kVA Static Switch FrontRear Front view Inverter Input 120 to 1200 kVA Static Switch CubiclesDetails of earthing connections in the various cubicles Rectifier-inverter cubicleKVA Static Switch Cubicles Tele-Monitor unitComz 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC