APC 9000 installation manual Internal connections between cubicles, XMGD05, XFGD06

Page 18

Installation

Internal connections between cubicles

removal of inverter leg no.6 is recommended prior to bolting fish-plates L+ and L-;

first remove the two fuses and the two cables connected to the leg;

then pull the leg out;

bolt fish-plates L+ and L-;

refit inverter leg no 6;

intended only for transportation, the front gussets do not need to be refitted;

bolt cables L1, L2, L3 and N (4 x 2) coming from the left cubicle to the bars in the right cubicle (see figure opposite);

connect the earth strap to the front uprights of both cubicles;

connect the connectors marked XF286 to XF2810 on the five ribbon cables coming from the right cubicle to connectors XM286 to XM2810 respectively on the interface board located on the right side of the left cubicle;

connect the connectors marked XFGD01 to XFGD05 (XFGD01 to XFGD05 and XMGD06 for parallel UPSs) on the control wires coming from the left cubicle to connectors XMGD01 to XMGD05 (XMGD01 to XMGD05 and XFGD06 for

parallel UPSs).

right cubicle

left cubicle

fuses and cables

XMGD05

 

to be disconnected

 

inverter

L

fish-plates

leg no. 6

 

to be

 

L+

bolted

interface board

 

 

XM286 to XM2810

 

 

 

 

cables to be

XMGD01 to XMGD04

 

connected

 

 

XFGD06

N

L1 L2 L3

 

earth strap to be

 

 

connected to the front

 

 

uprights of both cubicles

 

 

34006451EN/AC - Page 18

Image 18
Contents Installation manual Mgetm GalaxyTM34006451EN/AC Contents Characteristics Characteristics common to all cubiclesCharacteristics of Static Switch Cubicles Static Switch CubicleCharacteristics of rectifier-inverter cubicles Rectifier-inverter cubicleElectrical parameters for Mains 2 415 Electrical parameters for selecting protective devicesElectrical parameters for Mains Rated Mains 1 current InverterElectrical parameters for determining cable cross-sections Parameters for single-unit UPS cablesInstallation with parallel frequency converters Installation with parallel UPSs with a centralised SSCNF C 15-100 authorizes a maximum of 4 cables per phase Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Side clearances provided by the spacing uprights Rear HandingPositioning the cubicles FrontCubicle footpads Rear Floor loads figureCubicle layout on false floor or normal floor figures 6, 7 Connection via the bottomLayout for a single-unit UPS with one battery cubicle Rear Power circuit wiring diagrams Diagram for a frequency converter with batteriesSpecial case Diagram for a frequency converter without batteries Example of a 2 parallel UPS rectifier-inverters with SSC Modular UPS cubicle External maintenance bypass cubicle Cubicle mounting and connection Mounting of the left and right cubiclesInternal connections between cubicles XMGD05XFGD06 Left cubicle of single-unit or parallel UPS with SSC Connection of power circuitsGeneral Cross-section AAXR9 Right cubicle of single-unit UPSXR1 XR8 XR2 XR5 XR3 XR6 XR4 XR7XR2 XR5 Right cubicle of a parallel UPS with SSCFront Rear XR3 XR6 XR4 XR7Connection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Connections between Apoz boards Connection to battery circuit breaker QF1Emergency shutdown Connections between rectifier-inverter cubiclesXM XM XM XM Connections between Misi boards modular UPSs MisiUPS Misi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connection of the battery Temperature Monitor optional ConnectionsXR2 XR1 Temperature Monitor installation in a battery room Temperature Monitor baseDimensions of the Temperature Monitor 75 x 75 x 21 mm Final installation steps Connection of the LED remote indications unitMains 2 line protection Rated inverter output kVA Maximum permissible currentQ4S Cubicle mountingLeft cubicle XF1-XF2 XM1-XM2Right cubicle of a 2000 kVA Static Switch Front viewLeft cubicle of a 2000 kVA Static Switch FrontRear Front view Rectifier-inverter cubicle 120 to 1200 kVA Static Switch CubiclesDetails of earthing connections in the various cubicles Inverter InputKVA Static Switch Cubicles Tele-Monitor unitComz 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC