APC 9000 installation manual Electrical parameters for determining cable cross-sections

Page 7

Characteristics

1.5Electrical parameters for determining cable cross-sections

this table has been drawn up for rated phase-to-phase Mains and load voltages of 415 V. For voltages of 380 V, multiply the currents for Mains 2 and load by 1.09; for voltages of 400 V, use the table in another language version of this manual;

the current values and cable cross-sections for Mains 1 are given for full rated load with a power factor of 0.9 and a battery consuming its minimum float charging voltage;

the battery current values and cable cross-sections have been determined for a battery at the end of a charge cycle;

the current values and cable sections for Mains 2 and load are given for full rated load with a power factor of 0.9.

For frequency converters, the parameters concerning Mains 2 are not applicable.

The load parameters common to all the converters are given in the table below.

For a parallel UPS, the parameters for Mains 2 and load are also provided in the table below.

For a modular UPS, the parameters for Mains 2 and load are also provided in the table below.

Parameters for single-unit UPS cables

Copper conductors

rated

line currents absorbed in Amps

 

cross-sectional area of cables in mm2 (2)

inverter

Mains 1

415 V

battery

Mains 1

415 V

battery

output

 

Mains 2

 

 

Mains 2

 

in kVA

with or

 

with or

 

and load

 

and load

 

 

 

 

 

without

 

without

 

 

 

 

 

 

 

battery (1)

 

 

battery (1)

 

 

 

 

 

 

 

 

 

800

1455

1155

2274

4 x 240

4 x 185

3 x 240

900

1455

1299

2274

4 x 240

4 x 240

3 x 240

Aluminium conductors

rated

line currents absorbed in Amps

 

cross-sectional area of cables in mm2 (2)

inverter

 

 

 

 

 

 

Mains 1

415 V

battery

Mains 1

415 V

battery

output

 

Mains 2

 

 

Mains 2

 

in kVA

with or

 

with or

 

and load

 

and load

 

 

 

 

 

without

 

without

 

 

 

 

 

 

 

battery (1)

 

 

battery (1)

 

 

 

 

 

 

 

 

 

800

1455

1155

2274

4 x 400

4 x 300

3 x 400

900

1455

1299

2274

4 x 400

4 x 400

3 x 400

(1)the rated Mains 1 currents (In) have been determined for a minimum float charging voltage of 423 V and full rated load with a power factor of 0.9.

(2)the cable cross-sections are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m (AC circuits) or 25 m (DC circuits if cables not provided). For greater lengths, the cross-sections should be chosen to limit voltage drops to 3 % (AC)

or 1 % (DC).

34006451EN/AC - Page 7

Image 7
Contents Mgetm GalaxyTM Installation manual34006451EN/AC Contents Characteristics common to all cubicles CharacteristicsRectifier-inverter cubicle Static Switch CubicleCharacteristics of rectifier-inverter cubicles Characteristics of Static Switch CubiclesRated Mains 1 current Inverter Electrical parameters for selecting protective devicesElectrical parameters for Mains Electrical parameters for Mains 2 415Parameters for single-unit UPS cables Electrical parameters for determining cable cross-sectionsInstallation with parallel UPSs with a centralised SSC Installation with parallel frequency convertersNF C 15-100 authorizes a maximum of 4 cables per phase Maintenance Bypass cubicle Mains Inverter Mains 1 mains Load Front HandingPositioning the cubicles Side clearances provided by the spacing uprights RearConnection via the bottom Floor loads figureCubicle layout on false floor or normal floor figures 6, 7 Cubicle footpads RearLayout for a single-unit UPS with one battery cubicle Rear Diagram for a frequency converter with batteries Power circuit wiring diagramsSpecial case Example of a 2 parallel UPS rectifier-inverters with SSC Diagram for a frequency converter without batteriesModular UPS cubicle External maintenance bypass cubicle Mounting of the left and right cubicles Cubicle mounting and connectionXMGD05 Internal connections between cubiclesXFGD06 Cross-section AA Connection of power circuitsGeneral Left cubicle of single-unit or parallel UPS with SSCXR2 XR5 XR3 XR6 XR4 XR7 Right cubicle of single-unit UPSXR1 XR8 XR9XR3 XR6 XR4 XR7 Right cubicle of a parallel UPS with SSCFront Rear XR2 XR5XR1 XR2 XR3 XR4 Connection of auxiliary circuits on the remote relay boardConnections between rectifier-inverter cubicles Connection to battery circuit breaker QF1Emergency shutdown Connections between Apoz boardsXM XM XM XM Misi Connections between Misi boards modular UPSsUPS Misi XR8 XR9 XR5 XR6 XR7 Acpz board of the Static Switch CubicleConnections Connection of the battery Temperature Monitor optionalXR2 XR1 Temperature Monitor base Temperature Monitor installation in a battery roomDimensions of the Temperature Monitor 75 x 75 x 21 mm Connection of the LED remote indications unit Final installation stepsRated inverter output kVA Maximum permissible current Mains 2 line protectionXF1-XF2 XM1-XM2 Cubicle mountingLeft cubicle Q4SFront view Right cubicle of a 2000 kVA Static SwitchFront Left cubicle of a 2000 kVA Static SwitchRear Front view Inverter Input 120 to 1200 kVA Static Switch CubiclesDetails of earthing connections in the various cubicles Rectifier-inverter cubicleTele-Monitor unit KVA Static Switch CubiclesComz 34006451EN/AC 34006451EN/AC 34006451EN/AC 34006451EN/AC