Operation – Operation Procedures
Turn the internal mechanical bypass lever upwards to activate it. The load will now be supported directly by utility/mains power.
Reinstall the Front Panel.
Single System – turning into external bypass.
In bypass operation the batteries are still powered. If a total power off is required the batteries must be pulled out to the red disconnect line, see the section How to perform a total power off.
Warning
Chrg 100%
Load 000%
xxxVin 000Vout x0Hz Runtime: 0hr 0m
Use
UPS into Bypass Do Self Test Simulate Power Fail Start Runtime Cal
Press | Use |
|
|
| Press |
|
|
|
Control Logging
Status Display
Setup Diags
Help
Press | Use | Press |
| Confirm: |
|
| UPS into | Bypass |
| NO, ABORT |
|
| YES, UPS | into Bypass |
From the external MBP: Turn the bypass switch (Q003) to position “1” (ON).
If the UPS has to be completely isolated/ removed, see the section How to perform a total power off.
From the external MBP: Turn the output switch (Q002) to position “0” (OFF).
8 |