APC VT manual How to perform a total power off, Turn Load Off

Page 22

Operation – Operation Procedures

How to perform a total power off

Total power off – single system without MBP.

Mains

breaker

 

UPS

XR Enclosure

 

Check that the load is OFF.

From the UPS: Turn OFF the UPS from the

 

display via Control–Turn Load Off –Yes,

 

Turn Load Off.

From the XR Enclosure(s) (if available): Set the DC disconnect switch to the OFF position.

From the XR Enclosure(s) (if available): Disconnect the batteries by pulling them out to the red disconnect line shown on each battery unit.

From the UPS: Disconnect the batteries by pulling them out to the red disconnect line shown on each battery unit.

Set the utility/mains breaker to the OFF or LOCKED-OUTposition. If the UPS has dual utility/mains supply, set both supplies to the

OFF or LOCKED-OUT position.

WARNING!

The lockout procedures at utility/mains breaker must be followed. If necessary, install a Warning padlock.

16

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Image 22
Contents Operation Page About this Manual Companion manualsHow to find updates to this manual Contents Maintenance Safety Interface area OverviewUser Interface Display interfaceMain Menu Screen Menu tree Previous screens Operation Operation ModesOperation Procedures How to turn into bypassSingle System turning into external bypass Parallel System turning into external bypass How to turn into normal operation Control-UPS out of bypass-Yes, UPS out of bypassEach display via Control-Turn Load on How to turn load OFF/ON via the display interface How to view the Status screens Use the UP/DOWN keys to go through the parametersHow to view Logging and Statistics How to use the Diags screen Diags. View troubleshooting informationHow to perform a total power off Turn Load OffLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Settings ConfigurationHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings How to determine if you need a replacement part MaintenanceParts Replacement How to return parts to APCHow to store the battery modules Replaceable parts only trained personnelUser interface front How to replace a Network Management Card How to replace and install a battery module24 kg / 4 x 53 lbs   Xrups UPS / XR Status and Alarm Messages TroubleshootingDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 990-2282A-001 APC Worldwide Customer Support01/2007