APC VT manual Each display via Control-Turn Load on

Page 17

Operation – Operation Procedures

Parallel System – turning into normal operation from external bypass.

Never attempt to turn the UPS into normal operation till you have verified that there are no internal UPS faults.

Caution

From the external MBP: Turn all input

From the external MBP: Check that all the

switches (Q001) to position “1” (ON).

output lamps (Q002) are lit.

From the external MBP: Turn all output

From the UPS: Connect the batteries in the

switches (Q002) to position “1” (ON). The

UPS by pushing them in.

lamp indicator of the output isolation breaker

 

(Q004) is still lit.

 

From the XR Enclosure(s) (if available): Set

From the XR Enclosure(s) (if available):

the DC disconnect switch (if available) to the

Connect the batteries by pushing them in.

ON position.

 

From the UPS: Turn ON all UPS units from

From the external MBP: Check that all the

each display via Control–Turn Load ON–

lamps (Q002) are unlit.

Yes, Turn Load ON.

 

From the UPS: Turn the UPS units into

From the external MBP: Check that the lamp

bypass from one UPS display via Control–

indicator of the output isolation breaker is lit

UPS into bypass–Yes, UPS into bypass.

(Q004).

Check that the UPS units are in bypass. The

 

green (LOAD ON) and the yellow (BYPASS)

 

LEDs are lit.

 

From the external MBP: Turn the output isolation breaker (Q004) to position “1” (ON). Now the lamps (Q003 + Q004) are lit.

From the UPS: Turn the UPS units out of bypass from the display via ControlUPS out of bypassYes, UPS out of bypass.

From the external MBP: Turn the bypass switch (Q003) to position “0” (OFF). The lamps (Q004) are unlit, but (Q003) is lit until the UPS is running in normal operation.

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

11

Image 17
Contents Operation Page Companion manuals About this ManualHow to find updates to this manual Contents Maintenance Safety User Interface OverviewInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Modes OperationHow to turn into bypass Operation ProceduresSingle System turning into external bypass Parallel System turning into external bypass Control-UPS out of bypass-Yes, UPS out of bypass How to turn into normal operationEach display via Control-Turn Load on How to turn load OFF/ON via the display interface Use the UP/DOWN keys to go through the parameters How to view the Status screensHow to view Logging and Statistics Diags. View troubleshooting information How to use the Diags screenTurn Load Off How to perform a total power offLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on How to change the Clock and the Alarms in the Setting menu ConfigurationSettings  To go to Time Configuration Settings Parts Replacement MaintenanceHow to determine if you need a replacement part How to return parts to APCReplaceable parts only trained personnel How to store the battery modulesUser interface front How to replace and install a battery module How to replace a Network Management Card24 kg / 4 x 53 lbs   Xrups UPS / XR Display messages TroubleshootingStatus and Alarm Messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 01/2007 APC Worldwide Customer Support990-2282A-001