Operation – Operation Procedures

How to turn into normal operation

Single System – turning into normal operation from internal bypass.

Never attempt to switch back the UPS into normal operation till you have verified that there are no internal UPS faults.

Caution

Check that the UPS is in bypass. The green

(LOAD ON) and the yellow (BYPASS) LEDs are lit.

Press ESC to return to the previous menus and turn out of bypass from the display via

Control–UPS out of bypass–Yes, UPS out of bypass.

Turn the mechanical bypass lever downwards into a horizontal position to deactivate the internal bypass operation.

Check that the UPS is in normal operation. The yellow (BYPASS) LED turns off and the green (LOAD ON) LED remains lit.

Single System – turning into normal operation from external bypass.

Never attempt to switch back the UPS into normal operation till you have verified that there are no internal UPS faults.

Caution

From the external MBP: Turn the output switch (Q002) to position “1”(ON).

From the external MBP: Turn the bypass switch (Q003) to position “0” (OFF).

From the UPS: Check that the UPS is in normal operation. The yellow (BYPASS) LED turns off and the green (LOAD ON) LED remains lit.

From the UPS: Check that the yellow

(BYPASS) LED is lit and the green (LOAD ON) LED is lit.

From the UPS: Turn out of bypass from the display via Control–UPS out of bypass– Yes, UPS out of bypass.

10

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Image 16
Contents Operation Page About this Manual Companion manualsHow to find updates to this manual Contents Maintenance Safety Overview User InterfaceInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Operation ModesOperation Procedures How to turn into bypassSingle System turning into external bypass Parallel System turning into external bypass How to turn into normal operation Control-UPS out of bypass-Yes, UPS out of bypassEach display via Control-Turn Load on How to turn load OFF/ON via the display interface How to view the Status screens Use the UP/DOWN keys to go through the parametersHow to view Logging and Statistics How to use the Diags screen Diags. View troubleshooting informationHow to perform a total power off Turn Load OffLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Settings ConfigurationHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings Maintenance Parts ReplacementHow to determine if you need a replacement part How to return parts to APCHow to store the battery modules Replaceable parts only trained personnelUser interface front How to replace a Network Management Card How to replace and install a battery module24 kg / 4 x 53 lbs   Xrups UPS / XR Status and Alarm Messages TroubleshootingDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 990-2282A-001 APC Worldwide Customer Support01/2007