APC VT manual Total power off isolating one UPS in a parallel system

Page 24

Operation – Operation Procedures

Total power off – isolating one UPS in a parallel system.

From the UPS: From the Main Menu screen

From the UPS: Turn load OFF from the display

select Status and scroll down to Status of

on the UPS to be isolated via Control–Turn

actual redundancy: n+ in order to check that

Load off–Yes, turn Load off.

the remaining UPS(s) will be able to carry the

 

load when one UPS is isolated.

 

From the external MBP: Check that the output lamp (Q002) of the UPS to be isolated is lit.

From the external MBP: Turn the input switch (Q001) connected to the UPS you want to isolate to position “0” (OFF) .

From the UPS: Disconnect the batteries in the UPS which you want to isolate by pulling them out to the red disconnect line.

From the external MBP: Turn the output switch (Q002) connected to the UPS you want to isolate to position “0” (OFF).

From the XR Enclosure(s) (if available): Set the DC disconnect switch (if available) on the XR Enclosure to the OFF position.

From the XR Enclosure(s) (if available): Disconnect the batteries by pulling them out to the red disconnect line.

Parallel system – turning the isolated UPS into normal operation.

From the external MBP: Turn the input switch (Q1) connected to the UPS you want to turn into normal operation to position “1” (ON).

From the XR Enclosure(s) (if available): Connect the batteries by pulling them in.

From the external MBP: Turn the output

switch (Q002) connected to the UPS you want to turn into normal operation to position “I”

(ON).

From the UPS: Press ESC two times to get back to the Overview Screen.

From the UPS: Connect the batteries by pulling them in.

From the XR Enclosure(s) (if available): Set the DC disconnect switch (if available) on the XR Enclosure to position ON.

From the UPS: Turn load ON from the display on the UPS you want to turn into normal operation via Control–Turn Load on–Yes, turn Load on.

From the UPS: On the Overview Screen, check that the load percentage of the UPS units is approximately the same.

18

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Image 24
Contents Operation Page About this Manual Companion manualsHow to find updates to this manual Contents Maintenance Safety Overview User InterfaceInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Operation ModesOperation Procedures How to turn into bypassSingle System turning into external bypass Parallel System turning into external bypass How to turn into normal operation Control-UPS out of bypass-Yes, UPS out of bypassEach display via Control-Turn Load on How to turn load OFF/ON via the display interface How to view the Status screens Use the UP/DOWN keys to go through the parametersHow to view Logging and Statistics How to use the Diags screen Diags. View troubleshooting informationHow to perform a total power off Turn Load OffLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Configuration SettingsHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings Maintenance Parts ReplacementHow to determine if you need a replacement part How to return parts to APCHow to store the battery modules Replaceable parts only trained personnelUser interface front How to replace a Network Management Card How to replace and install a battery module24 kg / 4 x 53 lbs   Xrups UPS / XR Troubleshooting Status and Alarm MessagesDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page APC Worldwide Customer Support 990-2282A-00101/2007