APC VT manual How to perform a restart

Page 25

Operation – Operation Procedures

How to perform a restart

Restart – single system wihout external MBP.

Only trained personnel familiar with the construction and the equipment may

restart the UPS.

Warning

Set the utility/mains breaker to the ON position.

If your installation includes an XR Battery Enclosure (SUVTBXR2B6S/SUVTBXR6B6S) with a DC disconnect switch, set the DC disconnect switch to the ON position.

Wait approximately 30 seconds for the system to boot up and carry out a self test.

Note

After system boot-up, the display will automatically ask you to confirm/select voltage and frequency as shown in the following.

Voltage confirmation. At restart, the display will prompt you through the following screens:

Use

Confirm Voltage

Use 400V

Yes, use 400V

No, select another

Press Use

Apply load?

Yes

No

Press

When the Confirm Voltage prompt appears on the screen, go to the desired voltage using the UP/ DOWN keys and press ENTER.

When the prompt Apply load appears, go to Yes using the UP/DOWN keys and press ENTER if you want the UPS to provide a load output now. (If you do not want UPS load output at this point, go to No).

Chrg xxx%

Load xxx%

xxxVin xxxVout xxHz Run-time: xxhr xxmin

The green (LOAD ON) LED is now lit. Press ESC two times and the display will show the above Overview Screen.

The UPS is now ready to support the load.

Note

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

19

Image 25
Contents Operation Page Companion manuals About this ManualHow to find updates to this manual Contents Maintenance Safety User Interface OverviewInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Modes OperationHow to turn into bypass Operation ProceduresSingle System turning into external bypass Parallel System turning into external bypass Control-UPS out of bypass-Yes, UPS out of bypass How to turn into normal operationEach display via Control-Turn Load on How to turn load OFF/ON via the display interface Use the UP/DOWN keys to go through the parameters How to view the Status screensHow to view Logging and Statistics Diags. View troubleshooting information How to use the Diags screenTurn Load Off How to perform a total power offLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Settings ConfigurationHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings Parts Replacement MaintenanceHow to determine if you need a replacement part How to return parts to APCReplaceable parts only trained personnel How to store the battery modulesUser interface front How to replace and install a battery module How to replace a Network Management Card24 kg / 4 x 53 lbs   Xrups UPS / XR Status and Alarm Messages TroubleshootingDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 990-2282A-001 APC Worldwide Customer Support01/2007