APC VT manual Display Message Meaning Corrective Action

Page 42

Troubleshooting – Status and Alarm Messages

Display Message

Meaning

Corrective Action

 

 

 

System Not Synchro-

The system cannot synchronize to

Option 1: Decrease the input fre-

nized to Bypass.

bypass. The mode may not be avail-

quency sensitivity.

 

able.

Contact APC Customer Support

 

 

(see back cover).

 

 

Option 2: Correct the bypass input

 

 

voltage to provide acceptable voltage

 

 

on frequency.

 

 

 

UPS In Bypass Due To

The UPS has transferred to Bypass

Contact APC Customer Support

Fault.

Mode because a fault has occurred.

(see back cover).

 

 

 

UPS In Bypass Due To

The load exceeded the power

Decrease the load.

Overload.

capacity. The UPS has switched to

 

 

Bypass Mode.

 

 

 

 

UPS Is Overloaded.

The load exceeded the system power

Option 1: Decrease the load.

 

capacity.

Option 2: Check the load distribution

 

 

on the 3 phases via the display. If the

 

 

load is unevenly distributed, adjust

 

 

the load distribution.

 

 

 

Weak Batt(s) Detected.

One or more weak batteries detected.

Replace the weak batteries.

Reduced Runtime.

 

 

 

 

 

XR Battery Fuse Blown.

XR Battery Fuse blown. Runtime is

Replace the blown fuse in XR Enclo-

 

lower than expected.

sure (only applicable if your installa-

 

 

tion includes an XR

 

 

Enclosure).

 

 

 

36

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Image 42
Contents Operation Page About this Manual Companion manualsHow to find updates to this manual Contents Maintenance Safety Interface area OverviewUser Interface Display interfaceMain Menu Screen Menu tree Previous screens Operation Operation ModesOperation Procedures How to turn into bypassSingle System turning into external bypass Parallel System turning into external bypass How to turn into normal operation Control-UPS out of bypass-Yes, UPS out of bypassEach display via Control-Turn Load on How to turn load OFF/ON via the display interface How to view the Status screens Use the UP/DOWN keys to go through the parametersHow to view Logging and Statistics How to use the Diags screen Diags. View troubleshooting informationHow to perform a total power off Turn Load OffLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Configuration SettingsHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings How to determine if you need a replacement part MaintenanceParts Replacement How to return parts to APCHow to store the battery modules Replaceable parts only trained personnelUser interface front How to replace a Network Management Card How to replace and install a battery module24 kg / 4 x 53 lbs   Xrups UPS / XR Troubleshooting Status and Alarm MessagesDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page APC Worldwide Customer Support 990-2282A-00101/2007