APC VT manual Parallel System turning into external bypass

Page 15

Operation – Operation Procedures

Parallel System – turning into external bypass.

In bypass operation the batteries are still charged. If a total power off is required, the batteries must be pulled out to the red disconnect line, see the section How to perform a total power off.

Warning

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Use

UPS into Bypass Do Self Test Simulate Power Fail Start Runtime Cal

Press

Use

Press

 

Control

Logging

 

Status

Display

 

Setup

Diags

 

 

Help

Press

Use

Press

 

Confirm:

 

 

UPS into

Bypass

 

NO, ABORT

 

 

YES, UPS

into Bypass

From the UPS: Check that all UPS units are in bypass on each of the displays.

From the external MBP: Turn the bypass switch (Q003) to position “1” (ON).

From the external MBP: Turn the output isolation breaker (Q004) to position “0” (OFF).

From the external MBP: Check that all output lamps are lit (Q002).

From the external MBP: Turn all input switches (Q001) to position “0” (OFF).

From the UPS: Disconnect the batteries by pulling them out to the red disconnect line.

For a total UPS shut down see the section How to perform a total power off.

From the external MBP: Check that the bypass lamp indication is lit (Q003).

From the external MBP: Check that the lamp

indication of the output isolation breaker is lit (Q004).

From the UPS: Turn OFF each UPS from the display via Control Turn Load off Yes, Turn Load off.

From the external MBP: Turn all output switches (Q002) to position “0” (OFF).

From the XR Enclosure(s) (if available): Set the DC disconnect switch (if available) to position OFF.

From the XR Enclosure(s) (if available): Disconnect the batteries by pulling them out to the red disconnect line.

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

9

Image 15
Contents Operation Page Companion manuals About this ManualHow to find updates to this manual Contents Maintenance Safety Display interface OverviewUser Interface Interface areaMain Menu Screen Menu tree Previous screens Operation Modes OperationHow to turn into bypass Operation ProceduresSingle System turning into external bypass Parallel System turning into external bypass Control-UPS out of bypass-Yes, UPS out of bypass How to turn into normal operationEach display via Control-Turn Load on How to turn load OFF/ON via the display interface Use the UP/DOWN keys to go through the parameters How to view the Status screensHow to view Logging and Statistics Diags. View troubleshooting information How to use the Diags screenTurn Load Off How to perform a total power offLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Configuration SettingsHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings How to return parts to APC MaintenanceParts Replacement How to determine if you need a replacement partReplaceable parts only trained personnel How to store the battery modulesUser interface front How to replace and install a battery module How to replace a Network Management Card24 kg / 4 x 53 lbs   Xrups UPS / XR Troubleshooting Status and Alarm MessagesDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page APC Worldwide Customer Support 990-2282A-00101/2007