APC VT manual How to view the Status screens, Use the UP/DOWN keys to go through the parameters

Page 19

How to view the Status screens

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Press Use

Operation – Operation Procedures

Press

Control Logging

Status Display

Setup Diags

Help

Use the UP/DOWN keys to go through the parameters:

View

Parameters

 

 

Voltage on all

Utility/mains voltage (V), bypass voltage (V), and output voltage (V) for each phase.

phases

 

 

 

Current on all

Utility/mains current (A), bypass current (A), and output current (A) for each phase.

phases

 

 

 

kVA and kW

Apparent power (kVA) and real power (kW) generated by the UPS and the connected

 

load.

 

 

Frequencies

Utility/mains frequency, bypass frequency, and output frequency in Hertz (Hz).

 

 

Load and batteries

Load: Percentage of the load in relation to the total UPS capacity.

 

 

Bat Voltage

Shows either the positive or negative half of the battery voltage (the lower value of the

 

two will appear).

 

 

Bat Cap

Percentage charge on the batteries in relation to the total battery capacity.

 

Runtime: The predicted runtime at the present load.

 

 

Batteries

Bat AmpHr: Battery capacity, including both external and internal batteries.

 

UPS Temp: The highest external battery temperature.

 

 

Alarm thresholds

Load: An alarm will be set when the load is above the threshold level.

 

Runtime: An alarm will be set when the runtime is below the threshold level.

 

 

Parallel Status

Local UPS is slave/master:

 

# of UPSs OK: Indicates the number of parallel UPS units that is OK.

 

# of UPSs fail: Indicates the number of parallel UPS that has failed.

 

 

Par load Status

KVA and KW: Total apparent power (kVA) and real power (kW) generated by the

 

parallel UPS units and the connected load.

 

Par redundancy: n+1, an alarm will be set if the redundancy level is below the threshold

 

level.

 

 

Parallel Operation

The parallel operation mode can be off, load on, requested bypass, in bypass due to fault

Mode

or maintenance.

 

 

Press the ESC key to return to the previous menus.

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

13

Image 19
Contents Operation Page Companion manuals About this ManualHow to find updates to this manual Contents Maintenance Safety Display interface OverviewUser Interface Interface areaMain Menu Screen Menu tree Previous screens Operation Modes OperationHow to turn into bypass Operation ProceduresSingle System turning into external bypass Parallel System turning into external bypass Control-UPS out of bypass-Yes, UPS out of bypass How to turn into normal operationEach display via Control-Turn Load on How to turn load OFF/ON via the display interface Use the UP/DOWN keys to go through the parameters How to view the Status screensHow to view Logging and Statistics Diags. View troubleshooting information How to use the Diags screenTurn Load Off How to perform a total power offLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Settings ConfigurationHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings How to return parts to APC MaintenanceParts Replacement How to determine if you need a replacement partReplaceable parts only trained personnel How to store the battery modulesUser interface front How to replace and install a battery module How to replace a Network Management Card24 kg / 4 x 53 lbs   Xrups UPS / XR Status and Alarm Messages TroubleshootingDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 990-2282A-001 APC Worldwide Customer Support01/2007