Maintenance – Parts Replacement

How to remove and install battery locks (if available). If your system is equipped with Battery

Locks, follow the below procedure to remove the battery locks.

Remove the M6 screw attaching the battery lock to the shelf.

Push the battery lock to the left, push it upwards and remove.

Use reverse procedures for installation of battery locks.

Replacement.

Batteries must be replaced by trained personnel only (see the section General safety prior to Battery Module replacement).

Caution

Directions for replacement. APC recommends that a whole battery module (four batteries) is replaced at the same time to ensure optimal runtime (see Example 1). However, it is only necessary to replace two batteries at the same time according to Example 2 and 3 in the below tables.

523mm/(20in)

Col A

Col B

Col C

Col D

Enclosure

 

 

 

 

 

 

 

 

 

Example 1

New

New

New

New

 

 

 

 

 

Example 2

New

New

Old

Old

 

 

 

 

 

Example 3

Old

Old

New

New

 

 

 

 

 

 

 

 

 

 

352mm/(14 in)

Col A

Col B

 

 

Enclosure

 

 

 

 

 

 

 

 

 

 

 

Example 1

New

New

 

 

 

 

 

 

 

New

New

 

 

 

 

 

 

 

Example 2

New

New

 

 

 

 

 

 

Old

Old

 

 

 

 

 

 

 

 

 

 

Example 3

Old

Old

 

 

 

 

 

 

New

New

 

 

 

 

 

 

 

 

 

 

30

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Image 36
Contents Operation Page About this Manual Companion manualsHow to find updates to this manual Contents Maintenance Safety Overview User InterfaceInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Operation ModesOperation Procedures How to turn into bypassSingle System turning into external bypass Parallel System turning into external bypass How to turn into normal operation Control-UPS out of bypass-Yes, UPS out of bypassEach display via Control-Turn Load on How to turn load OFF/ON via the display interface How to view the Status screens Use the UP/DOWN keys to go through the parametersHow to view Logging and Statistics How to use the Diags screen Diags. View troubleshooting informationHow to perform a total power off Turn Load OffLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Configuration SettingsHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings Maintenance Parts ReplacementHow to determine if you need a replacement part How to return parts to APCHow to store the battery modules Replaceable parts only trained personnelUser interface front How to replace a Network Management Card How to replace and install a battery module24 kg / 4 x 53 lbs   Xrups UPS / XR Troubleshooting Status and Alarm MessagesDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page APC Worldwide Customer Support 990-2282A-00101/2007