APC VT manual Operation Procedures, How to turn into bypass

Page 13

Operation Procedures

How to turn into bypass

Single System – turning into internal bypass.

The load is not protected by the UPS and the power is not conditioned when the internal mechanical bypass lever is activated.

Caution

In bypass operation the batteries are still charged. If a total power off is required, the batteries must be pulled out to the red disconnect line, see the section How to perform a total power off.

Warning

This procedure is not applicable to parallel systems as the internal mechanical bypass lever is unavailable.

Note

If the UPS is running and controllable through the display, carry out steps 1 through 5. If not, go directly to step 6.

Note

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Use

UPS into Bypass Do Self Test Simulate Power Fail Start Runtime Cal

Press

Use

Press

 

Control

Logging

 

Status

Display

 

Setup

Diags

 

 

Help

Press

Use

Press

 

Confirm:

 

 

UPS into

Bypass

 

NO, ABORT

 

 

YES, UPS

into Bypass

Check that the UPS is in bypass. The green

Remove the Front Panel from the UPS (see

(LOAD ON) and the yellow (BYPASS) LEDs

the Receiving and Unpacking sheet referred

are lit.

to under the section Companion manuals).

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

7

Image 13
Contents Operation Page Companion manuals About this ManualHow to find updates to this manual Contents Maintenance Safety User Interface OverviewInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Modes OperationHow to turn into bypass Operation ProceduresSingle System turning into external bypass Parallel System turning into external bypass Control-UPS out of bypass-Yes, UPS out of bypass How to turn into normal operationEach display via Control-Turn Load on How to turn load OFF/ON via the display interface Use the UP/DOWN keys to go through the parameters How to view the Status screensHow to view Logging and Statistics Diags. View troubleshooting information How to use the Diags screenTurn Load Off How to perform a total power offLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Settings ConfigurationHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings Parts Replacement MaintenanceHow to determine if you need a replacement part How to return parts to APCReplaceable parts only trained personnel How to store the battery modulesUser interface front How to replace and install a battery module How to replace a Network Management Card24 kg / 4 x 53 lbs   Xrups UPS / XR Status and Alarm Messages TroubleshootingDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 990-2282A-001 APC Worldwide Customer Support01/2007