Configuration – Settings
To go to Time
Use
Date:
Time: 13:45:51
The procedure to change the Time features is
Press | the same as described for date and month |
Press
to return to previous screen(s)
Alarm thresholds. The procedure for changing the Alarm thresholds is the same as described under the Clock changes. Please be aware of the below notes.
If the load level exceeds the
Note
Redundancy: The state of redundancy that will trigger an alarm: Choices are:
• N+0 – The power requirement exceeds the redundancy limit: Redundancy is not available.
Note
•N+1 – The power requirement does not utilize the last unit: Redundancy is available.
•N+2 – The power requirement does not utilize the last two units: Redundancy is available.
•N+3 – The power requirement does not utilize the last three units: Redundancy is available.
How to change the Beeper setup, the Contrast, and the Language in the Display menu
Chrg xxx% Load xxx% xxxxVin Runtime
Control Display
Status Diags
Setup Help
Logging
Display
Beeper setup
Display setup Contrast
Language
Work your way through the menu screens and make your changes with the UP/DOWN and the ENTER keys as described for the Clock and the Alarms in the Settings menu.
23 |