Troubleshooting – Status and Alarm Messages

 

 

 

 

 

Display Message

Meaning

 

Corrective Action

 

 

 

 

 

 

PBus Communication

Communication fault detected on the

 

Check PBUS 1 or PBus 2 wiring.

 

Fault on Cable 2.

PBus 1 or PBus 2.

 

If this does not help contact APC.

 

 

 

 

 

 

PBus Termination Fault

PBus 1 or PBus 2

 

Check if termination is present. If this

 

on Cable 1.

termination is missing.

 

does not help contact APC.

 

 

 

 

 

 

PBus Termination Fault

PBus 1 or PBus 2

 

Check if termination is present. If this

 

on Cable 2.

termination is missing.

 

does not help contact APC.

 

 

 

 

 

 

Parallel Configuration

The parallel system has not been con-

 

Contact APC.

 

Fault.

figured correct.

 

 

 

 

 

 

 

 

Parallel Redundancy

The parallel redundancy has been

 

No corrective action is necessary.

 

Restored.

restored.

 

 

 

 

 

 

 

 

Replace Batt(s).

One or more Battery Modules need

 

See the section How to replace and

 

 

replacement (only applicable with

 

install a battery module for proce-

 

 

internal batteries).

 

dures.

 

 

 

 

 

 

Runtime Is Below Alarm

The predicted runtime is lower than

 

Option 1: Allow the battery modules

 

Threshold.

the user-specified minimum runtime

 

to recharge.

 

 

alarm threshold. Either the battery

 

Option 2: If possible, increase the

 

 

capacity has decreased, or the load

 

number of battery modules.

 

 

has increased.

 

Option 3: Reduce the load.

 

 

 

 

Option 4: Decrease the alarm

 

 

 

 

threshold.

 

 

 

 

Contact APC Customer Support

 

 

 

 

(see back cover).

 

 

 

 

 

 

Site Wiring Fault.

Wrong phase rotation on the input

 

An electrician should check that the

 

 

side. The UPS will continue to supply

 

UPS has been wired properly.

 

 

conditioned power from batt.

 

 

 

 

 

 

 

 

Shutdown Due To Low

The UPS was in Battery Operation

 

No corrective action is necessary.

 

Battery.

and shut down the load when no more

 

Note: If the problem reoccurs, con-

 

 

battery power was available.

 

sider increasing the battery capacity.

 

 

 

 

 

 

Static Bypass Switch

The Static Bypass Switch has failed.

 

Contact APC Customer Support (see

 

Fault.

 

 

back cover).

 

 

 

 

 

 

System Failure Detected

The system has detected an internal

 

Check for other alarms and contact

 

by Surveillance.

error.

 

APC customer support if the problem

 

 

 

 

persists.

 

 

 

 

 

 

System Start Up

System configuration error. Unable to

 

Check for other alarms and contact

 

Configuration Failed.

determine system voltage and/or

 

APC customer support if the problem

 

 

Enclosure size.

 

persists.

 

 

 

 

 

 

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

35

Image 41
Contents Operation Page Companion manuals About this ManualHow to find updates to this manual Contents Maintenance Safety User Interface OverviewInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Modes OperationHow to turn into bypass Operation ProceduresSingle System turning into external bypass Parallel System turning into external bypass Control-UPS out of bypass-Yes, UPS out of bypass How to turn into normal operationEach display via Control-Turn Load on How to turn load OFF/ON via the display interface Use the UP/DOWN keys to go through the parameters How to view the Status screensHow to view Logging and Statistics Diags. View troubleshooting information How to use the Diags screenTurn Load Off How to perform a total power offLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on How to change the Clock and the Alarms in the Setting menu ConfigurationSettings  To go to Time Configuration Settings Parts Replacement MaintenanceHow to determine if you need a replacement part How to return parts to APCReplaceable parts only trained personnel How to store the battery modulesUser interface front How to replace and install a battery module How to replace a Network Management Card24 kg / 4 x 53 lbs   Xrups UPS / XR Display messages TroubleshootingStatus and Alarm Messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 01/2007 APC Worldwide Customer Support990-2282A-001