Operation – Operation Procedures

For details on how to remove Battery Locks (if available) see the section How to remove and install battery locks (if available).

Total power off – single system with MBP.

 

Check that the load is OFF.

From the UPS: Turn load OFF the UPS from

 

the display via Control–Turn Load off–Yes,

 

turn Load off.

From the external MBP: Turn the output switch (Q002) to position “0” (OFF).

From the XR Enclosure(s) (if available): Set the DC disconnect switch (if available) on the XR Enclosure(s) to the OFF position.

From the XR Enclosure(s) (if available): Disconnect the batteries by pulling them out to the red disconnect line.

From the external MBP: Turn the input switch (Q001) to position “0” (OFF).

From the UPS: Disconnect the batteries in the UPS by pulling them out to the red disconnect line.

Total power off – parallel system.

Check that the load is OFF.

From the UPS: Turn load OFF each of the UPS units from the display via ControlTurn

Load off–Yes, turn Load off.

From the external MBP: Turn the output isolation breaker (Q004) to position “0” (OFF).

From the external MBP: Turn all input switches (Q001) to position “0” (OFF).

From the UPS: Disconnect the batteries in the UPS units by pulling them out to the red disconnect line.

From the external MBP: Turn all output switches (Q002) to position “0” (OFF).

From the XR Enclosure(s) (if available): Set the DC disconnect switch (if available) to the OFF position.

From the XR Enclosure(s) (if available): Disconnect the batteries on the UPS units by pulling them out to the red disconnect line.

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

17

Image 23
Contents Operation Page Companion manuals About this ManualHow to find updates to this manual Contents Maintenance Safety Display interface OverviewUser Interface Interface areaMain Menu Screen Menu tree Previous screens Operation Modes OperationHow to turn into bypass Operation ProceduresSingle System turning into external bypass Parallel System turning into external bypass Control-UPS out of bypass-Yes, UPS out of bypass How to turn into normal operationEach display via Control-Turn Load on How to turn load OFF/ON via the display interface Use the UP/DOWN keys to go through the parameters How to view the Status screensHow to view Logging and Statistics Diags. View troubleshooting information How to use the Diags screenTurn Load Off How to perform a total power offLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on How to change the Clock and the Alarms in the Setting menu ConfigurationSettings  To go to Time Configuration Settings How to return parts to APC MaintenanceParts Replacement How to determine if you need a replacement partReplaceable parts only trained personnel How to store the battery modulesUser interface front How to replace and install a battery module How to replace a Network Management Card24 kg / 4 x 53 lbs   Xrups UPS / XR Display messages TroubleshootingStatus and Alarm Messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 01/2007 APC Worldwide Customer Support990-2282A-001