APC VT manual How to store the battery modules, Replaceable parts only trained personnel

Page 32

Maintenance – Parts Replacement

How to store the battery modules

The battery modules must be stored indoors and with their protective packaging still in place.

Ambient temperature:

-15° to 40°C/5°F to 104°F

Relative Humidity:

25-85% Non-condensing

Storage place free from vibration, dust, direct sunlight, and moisture.

Stored batteries should be recharged at regular intervals depending on the storage temperature:

Storage Temperature

Recharge interval

 

 

-15° to 20°C/5°F to 68°F

9 months

 

 

20° to 30°C/68°F to 86°F

6 months

 

 

30° to 40°C/86°F to 104°F

3 months

 

 

Caution: Do not store the batteries for more than 12 months.

Replaceable parts (only trained personnel).

Part

APC Part No.

 

 

Battery Module

SYBT4

Network Management Card with temperature sensor

AP9619

 

 

APC recommends that a whole battery module (four batteries) is replaced at the same time to ensure optimal runtime. However, it is only necessary to replace two batteries at the same time. See section How to replace and install a battery module, Directions for replacement.

Note

26

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Image 32
Contents Operation Page About this Manual Companion manualsHow to find updates to this manual Contents Maintenance Safety Overview User InterfaceInterface area Display interfaceMain Menu Screen Menu tree Previous screens Operation Operation ModesOperation Procedures How to turn into bypassSingle System turning into external bypass Parallel System turning into external bypass How to turn into normal operation Control-UPS out of bypass-Yes, UPS out of bypassEach display via Control-Turn Load on How to turn load OFF/ON via the display interface How to view the Status screens Use the UP/DOWN keys to go through the parametersHow to view Logging and Statistics How to use the Diags screen Diags. View troubleshooting informationHow to perform a total power off Turn Load OffLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on How to change the Clock and the Alarms in the Setting menu ConfigurationSettings  To go to Time Configuration Settings Maintenance Parts ReplacementHow to determine if you need a replacement part How to return parts to APCHow to store the battery modules Replaceable parts only trained personnelUser interface front How to replace a Network Management Card How to replace and install a battery module24 kg / 4 x 53 lbs   Xrups UPS / XR Display messages TroubleshootingStatus and Alarm Messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page 01/2007 APC Worldwide Customer Support990-2282A-001