Maintenance – Parts Replacement
How to store the battery modules
The battery modules must be stored indoors and with their protective packaging still in place.
Ambient temperature:
Relative Humidity:
Storage place free from vibration, dust, direct sunlight, and moisture.
Stored batteries should be recharged at regular intervals depending on the storage temperature:
Storage Temperature | Recharge interval |
|
|
9 months | |
|
|
20° to 30°C/68°F to 86°F | 6 months |
|
|
30° to 40°C/86°F to 104°F | 3 months |
|
|
Caution: Do not store the batteries for more than 12 months.
Replaceable parts (only trained personnel).
Part | APC Part No. |
|
|
Battery Module | SYBT4 |
Network Management Card with temperature sensor | AP9619 |
|
|
APC recommends that a whole battery module (four batteries) is replaced at the same time to ensure optimal runtime. However, it is only necessary to replace two batteries at the same time. See section How to replace and install a battery module, Directions for replacement.
Note
26 |