APC VT manual How to turn load OFF/ON via the display interface

Page 18

Operation – Operation Procedures

How to turn load OFF/ON via the display interface

Disconnecting the UPS output to the load does NOT de-energize the UPS! Always follow the total power off procedure if you need to de-energize the UPS in emergency Warning situations, see section How to perform a total power off!

Turn Load OFF – How to disconnect the UPS output to the load equipment.

Press Use

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Use

 

 

 

Press

Use

 

 

 

Turn Load Off

If the UPS is running in parallel operation this procedure must be carried out on each UPS.

Control

Logging

Status

Display

Setup

Diags

 

Help

Confirm:

Turn Load OFF

NO, Abort

YES, Turn Load OFF

Press

Press

Turn load ON – How to connect the UPS output to the load equipment.

Press Use

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Press

Control Logging

Status Display

Setup Diags

Help

Use

 

 

 

Press

Use

 

 

 

Turn Load On

Confirm:

Press

If the UPS is running in parallel operation this procedure must be carried out on each UPS.

Turn Load OFF

NO, Abort

YES, Turn Load ON

12

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Image 18
Contents Operation Page About this Manual Companion manualsHow to find updates to this manual Contents Maintenance Safety Interface area OverviewUser Interface Display interfaceMain Menu Screen Menu tree Previous screens Operation Operation ModesOperation Procedures How to turn into bypassSingle System turning into external bypass Parallel System turning into external bypass How to turn into normal operation Control-UPS out of bypass-Yes, UPS out of bypassEach display via Control-Turn Load on How to turn load OFF/ON via the display interface How to view the Status screens Use the UP/DOWN keys to go through the parametersHow to view Logging and Statistics How to use the Diags screen Diags. View troubleshooting informationHow to perform a total power off Turn Load OffLoad off-Yes, turn Load off Total power off isolating one UPS in a parallel system How to perform a restart Restart single system with MBP Load on- Yes, turn Load on Configuration SettingsHow to change the Clock and the Alarms in the Setting menu  To go to Time Configuration Settings How to determine if you need a replacement part MaintenanceParts Replacement How to return parts to APCHow to store the battery modules Replaceable parts only trained personnelUser interface front How to replace a Network Management Card How to replace and install a battery module24 kg / 4 x 53 lbs   Xrups UPS / XR Troubleshooting Status and Alarm MessagesDisplay messages Troubleshooting Status and Alarm Messages See the section How to replace Display Message Meaning Corrective Action Page APC Worldwide Customer Support 990-2282A-00101/2007