Install busbars
523 mm (20.59 in) UPS System with the UPS placed to the left (seen from the front).
XR2
XR1
UPS
1.Install the following baying kit busbars between the UPS and XR1:
880-1607 between the vertical busbar N on the UPS and busbar 4 on XR1
880-1606 between the vertical busbar (+) on the UPS and busbar 1 on XR1 880-1605 between busbar (-) on the UPS and busbar 6 on XR1
2.Install the following baying kit busbars between the two XR Battery Enclosures: 880-0926 between the vertical busbar 3 on XR1 and busbar 4 on XR2 880-0940 between the vertical busbar 2 on XR1 and busbar 1 on XR2 880-0941 between the vertical busbar 5 on XR1 and busbar 6 on XR2
12 | Smart-UPS VT ® 10-40 kVA 380/400/415 V, 208/220 V, 200/208 V Battery Installation |