DataNET Hub Specifications, Continued
Ambient Installation | Operation: | |
Conditions | ||
| ||
| ||
| (Purge with dry air or nitrogen if required in tropical conditions.) | |
| Must not be exposed to direct sunlight. | |
| Must be protected from rain. | |
| Storage and Transport: | |
Power | Nominal: | 115 Vac / 230 Vac (universal input) |
| Tolerance: | |
|
| 300 watts |
| Power line protection: G fuse element per IEC | |
| blow |
|
| Power wiring in field made to screw terminals on two part connectors; | |
| 16 AWG (1.5 mm) or smaller power wiring is accepted; must conform | |
| to local installation codes and requirements. If conformance to CE | |
| certified installation requirements is required, power cable must be | |
| shielded or installed in conduit. | |
Dual Hub Communication | Redundant system consisting of two identical Hub modules. Each | |
Modules | module consists of universal power supply and communications elec- | |
| tronics and nine DataNET port connections. | |
Protocol and Addressing | Open Systems standard TCP/IP protocol and addressing (Transmis- | |
| sion Control Protocol/Internet Protocol); Full Class A, B and C ad- | |
| dresses and subnet masking supported | |
Uplink Port Connections | 1 Uplink Port Cable or Fiber Optic Port Connection | |
| • Two part connectors with | |
| nection |
|
| • Fiber Optic Coupler for Fiber Optic Connections | |
Downlink Connections | 8 Downlink Cable or Fiber Optic Port Connections | |
| • Two part connectors with |
nection
• Fiber Optic Coupler for Fiber Optic Connections
Introduction • 7 |