Siemens DataNET Hub (DNH) user manual Repeat the procedure for each connected port on the Hub

Page 43

DataNET Hub Signal Equalizer Board, Continued

Switch Setting for Unknown Cable Lengths

Switch Settings for Known Cable Lengths

When cable lengths are unknown, or the cable is other than the recom- mended cable (Table 2-1.), signals must be compared at the Hub to identify which Equalizer board settings are needed. See page 37.

If the lengths of copper cable exceed those shown in Table 2-2, follow this procedure. See sample calculations page 36. This procedure will set switches SW1, SW2 and SW3 on the Signal Equalizer Board.

Step

Action

1.Measure and record the longest cable run (in Feet) con- nected from a device to any HUB port. The longest cable run does not require a Hub Signal Equalizer board.

2.Calculate the difference between the longest cable length and the length of cable connected to the port you wish to equalize.

3.Locate the difference in feet in the first column (Feet of Ca- ble) of Table 2-2.

4.Identify the correct Selection range in column two of Table 2-4 and set switches SW3, SW2 and SW1.

 

 

 

SW2

 

 

 

 

 

 

SW3

 

 

SW1

 

 

 

 

 

 

 

5.

Repeat the procedure for each connected port on the Hub

except the longest length that does not have an equalizer

 

 

board.

2000585-001

Installation 35

Image 43
Contents December User’s Manual 2000585-001 Advance DataNET Hub DNHCopyright Notice Table of Contents Table of Contents Preface Audience & Purpose Chapter ContentsGetting Help Before You Call Technical SupportSafety Practices and Precautions Safety Practices and Precautions Ports OverviewDescription Dual Hub ModulesAdvance Communi- cations System Package ConfigurationsEthernet Bridging DataNET Hub HierarchyDNH Links DataNET Hub OperationDNH and Maxum Com Boards Transparency DataNET SwitchingDefinitions DataNET Hub Specifications DataNET Hub Specifications DataNET Hub Specifications DataNET Cable Cable Type Vendors & P/N Installation NotesCommunication ComparisonsDataNET Hub Specifications DataNET Hub Specifications Zone 1 Wall Mount Dimension Table Description Metric InchesZone 1 Wall Mount Dimension Table Page Introduction Installation OverviewDescription Receipt of DNH Unpacking Reporting Damage Unpacking and InspectionInstructions Package Configurations Wall Mounting Wall or Rack Mounting InstallationRack Mounting CE Installations Wiring Requirements Description Wiring of Power to DataNET HUB Site Wiring RequirementsDataNET Channels Cable Cable Type Vendors & P/N Installation NotesRecommended DataNET CE Installations NEC Div 2 or Non Hazardous Areas Copper Wire Site RequirementsDataNET Fiber Optic Cable Connections Ethernet Communica- tion Links CE Installation Kit Instructions CE InstallationsCE Installations Before You Begin Wiring ConnectionsTypes of Connections Step Action AC Power Mains ConnectionsDNH Power Supply Installation Note Before You BeginInstall 15-Ampere circuit breakers, disconnect switches or AC Power Mains Connections Description Hubs DataNET Copper ConnectionsPort Connections DataNET Ports+ Important Cable Impedance SettingsMaster Port Connectors TB15 TB18 Signal Equalizer Board Downlink Wiring withoutDescription Instructions DataNET Hub Signal Equalizer BoardRepeat the procedure for each connected port on the Hub Calculation One Equalizer Board SettingsSample Calculations RecommendedExample Comparing SignalsOption 1. Connection Point Option 2. Connection Point View MeasurementsInstructions & Examples Step Action + 2.1 dB DataNET Fiber Optic Coupler DataNET Fiber Optic ConnectionsRX & TX Connections Fiber Optic Cable Type Port Connections Page Active Ethernet Port Ethernet ConnectionsPin No MDI Function 10BASE-T Cable RequirementsIntroduction Overview Command Line Definitions Important ChecklistTasks Check Chapter Preview Configuring Your PC Learning Hint Setting Network AddressConfiguring Your PC Click Terminal Settings button Configuring Your PC Establishing a Connection Before You Begin Password ProtectionGetting Started How to Change Password FormatHow to Log Out How to Log OnRemote Connection Log On At the prompt type login password IP AddressSetting Network Address Config address ip Available IP Addresses IP Address How to Assign an IP AddressAssigning an IP Address OverviewFirmware Updates MAC Address Con- figuration At the Local prompt type config address etherenetClick on Send Text File For monitoring the DNH operation System Status LEDsBoard Status LEDs Startup LED Status Advance DataNET Hub Communication boards have status LEDsGreen Normal LED Red Fault LEDYellow Warn LED Blink Codes Hub Port LEDsLED Ethernet Port LEDs Cross Link StatusConfiguration Conflicts TroubleshootingCabling errors Example Errors Configuration ParameterInstructions Signal Quality ProblemsTroubleshooting Description Unique Commands Command DescriptionsTimeout off Password passwordReset Timeout onConfig display Command Config netmask Command Config address ip command Config device id CommandConfig iproute Del Command Display Command Download Command Display links CommandExample local display links Dn setuptime Events Command Dn CommandCommand Descriptions Dn module on dn module off Help Command List Command Command DescriptionLogin Command Port Command Logout Command Netstat CommandExamplelocal netstat dn clear Test Command Timeout Command Trace Command Validation timeout Command Captured frames Verbose CommandParts Catalog Overview How to Place an OrderPart Description Ordering Number Available PartsAvailable Parts