Siemens DataNET Hub (DNH) user manual CE Installations, CE Installation Kit Instructions

Page 31

CE Installations

Description

This section should be used for installation sites that must conform to CE

 

(Conformite Europeene) Certification. Typically, this does not apply to

 

installations outside the EC unless the equipment was purchased with

 

the explicit requirements and expectations that it shall conform to EC

 

Electromagnetic and Radio Frequency Interference (EMI/RFI) rejection

 

specifications.

CE Installation Kit

Instructions

Available from Siemens Applied Automation CE Installation Kit P/N 2020264-001. This kit has all the parts for all the installations referenced in this section.

The following information pertains to CE Installation of General Purpose, Zone 1 and Division 2 Equipment. For Zone 1 Installations, all cabling is terminated in the DNH Zone 1 Enclosure.

Installation with Metallic

The preferred method is to route the field wiring in metallic conduit. If

Conduit

metallic conduit is used, unshielded power and signal wires can be used.

 

The power and signal wires (DataNET or Ethernet) must be routed in

 

separate conduit.

 

Using flexible conduit and/or armored cable is equivalent to using “steel

 

conduit”. Flexible conduit or armored cable must have its flexible conduit

 

and/or armoring conductivity 360-degree terminated at its entry to the

 

DNH enclosure (or bulkhead).

Installation without

If conduit is not used, the following installation practices must be used to

Metallic Conduit

ensure that the CE certification remains valid:

 

1. A shielded power cord or cable must be used for the input power

 

wiring. The shield must be terminated at the DNH in a 360-degree

 

termination at the enclosure (bulkhead); use Siemens Applied Auto-

 

mation P/N 2015729-001 contained in the CE Installation Kit or an

 

equivalent part. For Zone 1 Installation use Siemens Applied Auto-

 

mation P/N 1311001-014 Installation Kit.

 

2. The DataNET copper cables shields must be terminated in a 360-

 

degree termination at the enclosure (or bulkhead; use Siemens Ap-

 

plied Automation P/N 2015729-001 contained in the CE Installation

 

Kit or an equivalent part). For Zone 1 Installation, use Siemens Ap-

 

plied Automation P/N 13111001-014 Installation Kit.

2000585-001

Installation 23

Image 31
Contents December User’s Manual 2000585-001 Advance DataNET Hub DNHCopyright Notice Table of Contents Table of Contents Preface Audience & Purpose Chapter ContentsGetting Help Before You Call Technical SupportSafety Practices and Precautions Safety Practices and Precautions Ports OverviewDescription Dual Hub ModulesAdvance Communi- cations System Package ConfigurationsEthernet Bridging DataNET Hub HierarchyDNH Links DataNET Hub OperationDNH and Maxum Com Boards Transparency DataNET SwitchingDefinitions DataNET Hub Specifications DataNET Hub Specifications DataNET Hub Specifications DataNET Cable Cable Type Vendors & P/N Installation NotesCommunication ComparisonsDataNET Hub Specifications DataNET Hub Specifications Zone 1 Wall Mount Dimension Table Description Metric InchesZone 1 Wall Mount Dimension Table Page Introduction Installation OverviewDescription Receipt of DNH Unpacking Reporting Damage Unpacking and InspectionInstructions Package Configurations Wall Mounting Wall or Rack Mounting InstallationRack Mounting CE Installations Wiring Requirements Description Wiring of Power to DataNET HUB Site Wiring RequirementsDataNET Channels Cable Cable Type Vendors & P/N Installation NotesRecommended DataNET CE Installations NEC Div 2 or Non Hazardous Areas Copper Wire Site RequirementsDataNET Fiber Optic Cable Connections Ethernet Communica- tion Links CE Installation Kit Instructions CE InstallationsCE Installations Before You Begin Wiring ConnectionsTypes of Connections Step Action AC Power Mains ConnectionsDNH Power Supply Installation Note Before You BeginInstall 15-Ampere circuit breakers, disconnect switches or AC Power Mains Connections Description Hubs DataNET Copper ConnectionsPort Connections DataNET Ports+ Important Cable Impedance SettingsMaster Port Connectors TB15 TB18 Signal Equalizer Board Downlink Wiring withoutDescription Instructions DataNET Hub Signal Equalizer BoardRepeat the procedure for each connected port on the Hub Calculation One Equalizer Board SettingsSample Calculations RecommendedExample Comparing SignalsOption 1. Connection Point Option 2. Connection Point View MeasurementsInstructions & Examples Step Action + 2.1 dB DataNET Fiber Optic Coupler DataNET Fiber Optic ConnectionsRX & TX Connections Fiber Optic Cable Type Port Connections Page Active Ethernet Port Ethernet ConnectionsPin No MDI Function 10BASE-T Cable RequirementsIntroduction Overview Command Line Definitions Important ChecklistTasks Check Chapter Preview Configuring Your PC Learning Hint Setting Network AddressConfiguring Your PC Click Terminal Settings button Configuring Your PC Establishing a Connection Before You Begin Password ProtectionGetting Started How to Change Password FormatHow to Log Out How to Log OnRemote Connection Log On At the prompt type login password IP AddressSetting Network Address Config address ip Available IP Addresses IP Address How to Assign an IP AddressAssigning an IP Address OverviewFirmware Updates MAC Address Con- figuration At the Local prompt type config address etherenetClick on Send Text File For monitoring the DNH operation System Status LEDsBoard Status LEDs Startup LED Status Advance DataNET Hub Communication boards have status LEDsGreen Normal LED Red Fault LEDYellow Warn LED Blink Codes Hub Port LEDsLED Ethernet Port LEDs Cross Link StatusConfiguration Conflicts TroubleshootingCabling errors Example Errors Configuration ParameterInstructions Signal Quality ProblemsTroubleshooting Description Unique Commands Command DescriptionsTimeout off Password passwordReset Timeout onConfig display Command Config netmask Command Config address ip command Config device id CommandConfig iproute Del Command Display Command Download Command Display links CommandExample local display links Dn setuptime Events Command Dn CommandCommand Descriptions Dn module on dn module off Help Command List Command Command DescriptionLogin Command Port Command Logout Command Netstat CommandExamplelocal netstat dn clear Test Command Timeout Command Trace Command Validation timeout Command Captured frames Verbose CommandParts Catalog Overview How to Place an OrderPart Description Ordering Number Available PartsAvailable Parts