EXCEL 10 W7761A INPUT/OUTPUT DEVICE
GROUND | 5 | Analog ground |
|
|
|
4 | Analog Input 1 resistance | |
|
|
|
| 3 | Not Used |
|
|
|
| 2 | Not Used |
|
|
|
EGND | 1 | Earth Ground |
|
|
|
See Fig. 20 to wire a pneumatic transducer to a W7761A.
| + |
|
|
|
|
|
|
| C7770A AIR |
|
|
|
|
| |||
|
|
|
|
|
|
|
| TEMPERATURE SENSOR | |||||||||
24 VAC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
31 | 30 |
| 29 | 28 |
| 27 | 26 | 25 | 24 | 23 | 22 | 21 | 20 | 19 | 18 | 17 | 16 |
GND |
|
| GND | 24 VAC | 24 VAC COM | OUT 1 | OUT 2 | OUT 3 | OUT 4 | OUT 5 | OUT 6 | OUT 7 | OUT 8 | ||||
W7761A |
|
|
|
|
| TRIAC EQUIVALENT CIRCUIT |
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
REMOTE I/O |
|
|
|
|
|
|
|
|
|
|
| ||||||
DEVICE |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
E GND | NOT USED |
| NOT USED |
| GND | GND | GND | 22 VDC OUT | |||||||||
|
|
|
| ||||||||||||||
1 | 2 |
| 3 | 4 |
| 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | J3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 |
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 2 |
|
|
|
|
|
|
|
| |
1 |
| JACK FOR |
|
|
|
|
| ||||||||||
|
|
|
|
| SENSOR |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| GND |
|
|
|
|
|
|
| |||||
|
|
|
|
|
| NETWORK |
|
|
|
|
| ||||||
|
|
|
|
|
| ACCESS |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| T7770A |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| WALL |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| MODULE |
|
|
|
|
|
|
|
|
|
|
|
1EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.
2TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
M15276
Fig. 16. Typical T7770A and C7770A wiring diagram. (For note 2, refer to Fig. 15.)