Honeywell Broadcasting the Service Message, W7761A Device Status LED, Excel 10 Alarms

Page 37

 

 

 

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

 

 

 

 

 

 

 

Table 9. Excel 10 Alarms.

 

 

 

 

 

 

 

Alarm type

 

 

 

Name of alarm or error bit

number

Meaning of alarm code or error bit

 

 

 

 

 

RETURN_TO_NORMAL

128U

Return to no alarm after being in an alarm condition. This code is added

 

 

 

numerically to another alarm code to indicate that the alarm condition has

 

 

 

returned to normal.

 

 

 

 

 

ALARM_NOTIFY_DISABLED

255U

The alarm reporting has been turned off by the DestManMode. No more

 

 

 

alarms are reported via nvoAlarm until DestManMode turns on alarm repor

 

 

 

or upon application restart.

 

 

 

 

 

NO_ALARM

0

No alarms presently detected.

 

 

 

 

 

INPUT_NV_FAILURE

1

One or more NV inputs have failed in receiving an update within their spec

 

 

 

FAILURE_DETECT_TIME.

 

 

 

 

 

NODE_DISABLED

2

The control algorithm has stopped because the RIO device is in

 

 

 

DISABLED_MODE, MANUAL, or FACTORY_TEST mode. No more alarms

 

 

 

reported when the device is in the DISABLED_MODE. Alarms continue to

 

 

 

reported if the device is in the MANUAL or FACTORY_TEST mode. The

 

 

 

control is shut down and disabled until power is cycled or the node is reset

 

 

 

See note 1 below.

 

 

 

 

 

SENSOR_FAILURE

3

One or more sensors have failed.

 

 

 

 

 

NOTE: The node can be reset by switching the node to MANUAL and then to the normal operating mode.

Also, the Excel 10 variables, AlarmLogX where X is 1 through 5, that store the last five alarms to occur in the device, are available. These points can be viewed through XBS or E-Vision.

Broadcasting the Service Message

The Service Message allows a device on the E-Bus to be positively identified. The Service Message contains the device ID number and, therefore, can be used to confirm the physical location of a particular Excel 10 in a building.

There are two methods of broadcasting the Service Message from an Excel 10 W7761A Device. One uses a hardware service pin button on the side of the device (see Fig. 24). The other involves using the PC Configuration tool, as follows.

The commissioning tool is used to perform the ID Assignment task (see the E-Vision User’s Guide form, 74-2588).

SERVICE

PIN

BUTTON

M10094

Fig. 24. Location of the Service Pin Button.

W7761A Device Status LED

The LED on the front and center of a W7761A Device provides a visual indication of the status of the device. See Fig. 25. When the W7761A receives power, the LED should appear in one of the following allowable states (see Table 10):

37

74-2699

Image 37
Contents Excel 10 W7761A Remote Input/Output Device Appendices List of TablesTypical system overview Description of DevicesControl Provided Control ApplicationProducts Covered Organization of ManualProduct Names Abbreviations and Definitions Agency ListingsExcel 10 W7761A INPUT/OUTPUT Device Controllers ConstructionExcel 10 W7761A Remote I/O Device W7761A construction in in. mm List Of Available Points W7761A Performance Specifications PowerEnvironmental Operating Temperature Specified Space Temperature Sensing RangeShipping Temperature Memory CapacityOutdoor Air Temperature Discharge Air TemperatureReturn Air Temperature Mixed Air Temperature5585 Wall ModulesT7780 construction, subbase dimensions in in. mm ConfigurationsOccupancy Sensor Mixed-Output-Type ControlWindow Open/Closed Digital Input Wall Module OptionsPlan The System OverviewApplication Steps Step No Description Determine Other Bus Devices Required Lay Out Communications and Power WiringBus Layout 750,1$ Power Budget Calculation Example Power WiringLine Loss VA Ratings For Transformer Sizing Device DescriptionNema class 2 transformer voltage output limits VA RatingLine VOLTAGE` GREATER` Than 150 VAC General Considerations Prepare Wiring DiagramsW7761A Devices Terminal Number Description W7761A I/O DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Typical Pneumatic transducer Series 60 Floating to W7761A Bus Termination ModuleSee for E-Bus termination wiring options +$672 Excel 10 W7750 Controllers Order EquipmentT7770 Wall Modules SensorsEchelon Based Components and Parts AccessoriesCabling Temperature Degrees Excel 10 Alarms Broadcasting the Service MessageW7761A Device Status LED LED States T7780 Ddwm Bypass PushbuttonAdding Analog Inputs Enthalpy 4 to 20 mA Appendix A. Using E-Vision to Commission a W7761 DeviceAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Appendix B. Sequences of Operation Room Temperature Sensor RmTempCommon Operations Dirty Filter Monitor Window Sensor StatusWndwSeries 60 Modulating Control Pulse Width Modulating PWM ControlRelative Temperature Relative HumidityAir Flow CO 2 ConcentrationTable C1. Input/Output Points Left DefaultTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left SH MA DA EV HW MN TS Table C2. Control Parameters RightTable C3. Status Points Left NoalarmTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Right Table C5. Direct Access And Special Points LeftFig. D-1. Point capacity estimate for Zone Manager Approximate Memory Size Estimating ProcedureResistance Sensors Appendix E. Sensor Data for CalibrationSensor Type Sensor Use1956.79 Table E-4. Sensor Voltage Versus Humidity Voltage/Current SensorsHumidity Percentage Sensor Voltage C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts CO 2 Concentration PPM Sensor Voltage Table E-9. Sensor Voltage Versus CO 2 ConcentrationTable E-10. Sensor Voltage Versus Input Voltage To A/D Table E-11. Sensor Voltage Vdc Versus Pressure Inw Voltage to A/D Sensor VoltagePressure Inw kPa Sensor Voltage Vdc 3ODD