Honeywell W7761A specifications Table C5. Direct Access And Special Points Left

Page 70

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Table C5. Direct Access And Special Points (Left).

 

 

 

 

Digital

 

 

 

 

 

State

 

 

 

 

 

or

 

 

 

 

Engineering Units:

Value

 

 

 

 

English (Metric) or

of

 

User Address

NvName

Field Name

States plus Range

State

Default

 

 

 

 

 

 

DestManMode

nviManualMode

 

MODE_ENABLE

0

MODE_ENABLE

 

 

 

MODE_DISABLE

1

 

 

 

 

MODE_MANUAL

2

 

 

 

 

SUPPRESS_ALARMS

3

 

 

 

 

UNSUPPRESS_ALARMS

4

 

 

 

 

 

 

 

Table C5. Direct Access And Special Points (Right).

Share (SH), Map (MA), Direct Access (DA)

 

 

 

E-Vision (EV): Calibrate (C), Monitor (M),

 

 

 

 

Parameter (P), Schematic (S)

 

 

 

Hardware Configuration (HW),

 

 

 

 

Manual Point (MN), Test (TS)

 

 

 

 

 

 

 

 

 

 

 

 

SH

MA

 

DA

EV

HW

MN

 

TS

Comments

 

 

 

 

 

 

 

 

 

 

 

X

 

X

M P

 

 

 

 

DestManMode: is an input which is used to manually set the physical outputs.

 

 

 

 

 

 

 

 

 

DestManMode remains unchanged until another mode has been commanded or an

 

 

 

 

 

 

 

 

 

application restart has been performed. The valid enumerated values are:

 

 

 

 

 

 

 

 

 

MODE_ENABLE enables the node so that the RIO controls the physical outputs as

 

 

 

 

 

 

 

 

 

the normal mode. MODE_ENABLE is the default state after power is restored or an

 

 

 

 

 

 

 

 

 

application restart occurs. If the mode was MANUAL and DestManMode is set to

 

 

 

 

 

 

 

 

 

MODE_ENABLE, the node then goes through application restart.

 

 

 

 

 

 

 

 

 

MODE_DISABLED sets the node into the DISABLED mode. The alarm

 

 

 

 

 

 

 

 

 

NODE_DISABLED is initiated, and the physical outputs are turned off. The physical

 

 

 

 

 

 

 

 

 

inputs, network variable inputs, and network variable outputs are still functioning

 

 

 

 

 

 

 

 

 

when the node is in the DISABLED mode.

 

 

 

 

 

 

 

 

 

MODE_MANUAL sets the node into the MANUAL mode. The alarm

 

 

 

 

 

 

 

 

 

NODE_DISABLED is initiated, and the physical outputs are controlled manually as

 

 

 

 

 

 

 

 

 

commanded by DestManMode. The nodes configuration variables and

 

 

 

 

 

 

 

 

 

DestManMode are used to set valves, dampers, and/or digital output to the desired

 

 

 

 

 

 

 

 

 

manual positions or state(s). The physical inputs, network variable inputs, and

 

 

 

 

 

 

 

 

 

network variable outputs are still functioning when the node is in the MANUAL mode.

 

 

 

 

 

 

 

 

 

SUPPRESS_ALARMS causes AlarmType to be set to ALARM_NOTIFY_DISABLED,

 

 

 

 

 

 

 

 

 

and AlarmTypeLog to no longer record alarms. If alarms are suppressed,

 

 

 

 

 

 

 

 

 

UNSUPPRESS_ALARMS causes AlarmType and AlarmTypeLog to be returned to

 

 

 

 

 

 

 

 

 

reporting alarms. See nvoAlarm for more details. All unspecified values are the same

 

 

 

 

 

 

 

 

 

as MODE_ENABLE.

 

 

 

 

 

 

 

 

 

 

70

74-2699

Image 70
Contents Excel 10 W7761A Remote Input/Output Device List of Tables AppendicesDescription of Devices Typical system overviewProducts Covered Control ApplicationControl Provided Organization of ManualProduct Names Agency Listings Abbreviations and DefinitionsExcel 10 W7761A INPUT/OUTPUT Device Construction ControllersExcel 10 W7761A Remote I/O Device W7761A construction in in. mm Performance Specifications Power List Of Available Points W7761AShipping Temperature Specified Space Temperature Sensing RangeEnvironmental Operating Temperature Memory CapacityReturn Air Temperature Discharge Air TemperatureOutdoor Air Temperature Mixed Air TemperatureWall Modules 5585Configurations T7780 construction, subbase dimensions in in. mmWindow Open/Closed Digital Input Mixed-Output-Type ControlOccupancy Sensor Wall Module OptionsPlan The System OverviewApplication Steps Step No Description Determine Other Bus Devices Required Lay Out Communications and Power WiringBus Layout 750,1$ Power Wiring Power Budget Calculation ExampleVA Ratings For Transformer Sizing Device Description Line LossVA Rating Nema class 2 transformer voltage output limitsLine VOLTAGE` GREATER` Than 150 VAC General Considerations Prepare Wiring DiagramsW7761A Devices W7761A I/O Description Terminal Number DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Bus Termination Module Typical Pneumatic transducer Series 60 Floating to W7761ASee for E-Bus termination wiring options +$672 T7770 Wall Modules Order EquipmentExcel 10 W7750 Controllers SensorsAccessories Echelon Based Components and PartsCabling Temperature Degrees Excel 10 Alarms Broadcasting the Service MessageW7761A Device Status LED T7780 Ddwm Bypass Pushbutton LED StatesAppendix A. Using E-Vision to Commission a W7761 Device Adding Analog Inputs Enthalpy 4 to 20 mAAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Appendix B. Sequences of Operation Room Temperature Sensor RmTempCommon Operations Series 60 Modulating Control Window Sensor StatusWndwDirty Filter Monitor Pulse Width Modulating PWM ControlAir Flow Temperature Relative HumidityRelative CO 2 ConcentrationDefault Table C1. Input/Output Points LeftTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left Table C2. Control Parameters Right SH MA DA EV HW MN TSNoalarm Table C3. Status Points LeftTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Left Table C5. Direct Access And Special Points RightApproximate Memory Size Estimating Procedure Fig. D-1. Point capacity estimate for Zone ManagerSensor Type Appendix E. Sensor Data for CalibrationResistance Sensors Sensor Use1956.79 Table E-4. Sensor Voltage Versus Humidity Voltage/Current SensorsHumidity Percentage Sensor Voltage C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts CO 2 Concentration PPM Sensor Voltage Table E-9. Sensor Voltage Versus CO 2 ConcentrationTable E-10. Sensor Voltage Versus Input Voltage To A/D Table E-11. Sensor Voltage Vdc Versus Pressure Inw Voltage to A/D Sensor VoltagePressure Inw kPa Sensor Voltage Vdc 3ODD