Honeywell W7761A specifications Adding Digital Inputs

Page 41

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the E-Bus, that are used in the Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.

Table A-1. Supported Voltage And Current Input Sensors.

 

E-Vision Enumerated Name in the Input

RIO Network Variable that contains the

 

Application Selection Tab

Hardware Input Value

 

 

 

 

RA_Hum_C7600C

Humidity1 or Humidity2

 

 

 

 

OA_Hum_C7600C

Humidity1 or Humidity2

 

 

 

 

Filter_Diff_Pres

Pressure1 or Pressure2

 

 

 

 

RA_Hum_C7600B

Humidity1 or Humidity2

 

 

 

 

OA_Hum_C7600B

Humidity1 or Humidity2

 

 

 

 

RA_Enthalpy

CurrentAI

 

 

 

 

OA_Enthalpy

CurrentAI

 

 

 

 

Space_CO2

CO2Level

 

 

 

 

Voltage_Monitor

VoltageAI

 

 

 

ADDING DIGITAL INPUTS

 

See Table A-2 for the supported Digital input types that can be connected to the RIO Device. The user must add a software point (pseudo digital nstate - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant) through the Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA) sensor should be followed. The user will add a Pseudo Digital nstate point (<Vd>) in step one instead of the Pseudo Analog to the RIO CARE Plant and then use the Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the E-Bus, that are used in Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.

Table A-2. Supported Digital Input Types.

 

E-Vision Enumerated Name in the Input

RIO Network Variable that contains the

 

Application Selection Tab

Hardware Input Value

 

 

 

 

Digital Input 1:

SrcDigIn1Sts

 

Active_Short / Active_Open

 

 

 

 

 

Digital Input 2:

SrcDigIn2Sts

 

Active_Short / Active_Open

 

 

 

 

 

Digital Input 3:

SrcDigIn3Sts

 

Active_Short / Active_Open

 

 

 

 

 

Digital Input 4:

SrcDigIn4Sts

 

Active_Short / Active_Open

 

 

 

 

ADDING DIGITAL OUTPUTS

 

See Table A-3 for the supported digital output types that can be connected to the RIO Device.

The user must add a software point (pseudo analog) that can be mapped to the actual hardware output through the Custom Mapping function of E-Vision. The following procedure will instruct the user on adding the pseudo analog and using the Custom Mapping function so that the Digital Output can be used in the Zone Manager control strategy or switching logic, or be used with Excel 5000 controllers on the C-Bus.

1.With CARE running, open an existing RIO plant. The user can go into either switching logic or control strategy to add the pseudo analog point. If the user does not have an existing control loop through control strategy, use switching logic to add the pseudo point, otherwise a control loop will have to be created along with unnecessary RACL to add the point. This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into switching logic. Select the Software Points menu item and then Pseudo Analog. The Create/Select Software Point <Va> dialog box will be displayed. Type in a New point name for the Digital Output (such as MiscExhFan) and click on the OK button. The new point that was just created will be added to the screen as the header point for switching logic table and also added to the Point list. Select the Cancel button to exit the Create/Select Software Point <Va> dialog box. Exit switching logic by selecting the File menu item and Exit. CARE will display the Delete Unused Software Points list box. Click the Cancel button to continue.

2.Go into the Data Point Editor (Controller/Edit/Data Point Editor) and under Point select the pseudo analog point that was just created and the OK button. Select the drop down list for the Engineering Unit and scroll through the list until the Pct engineering units are displayed. Select the Pct engineering unit that is shown with one decimal place (number 55) and the OK button to save the selection. Cancel the User Address list box and select File/Exit to exit out of the Data Point Editor.

3.Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the Project and Export to E- Vision menu items. Type in the name of the Zone Manager Export file when the Export Zone Manager dialog box is

41

74-2699

Image 41
Contents Excel 10 W7761A Remote Input/Output Device Appendices List of TablesTypical system overview Description of DevicesControl Provided Control ApplicationProducts Covered Organization of ManualProduct Names Abbreviations and Definitions Agency ListingsExcel 10 W7761A INPUT/OUTPUT Device Controllers ConstructionExcel 10 W7761A Remote I/O Device W7761A construction in in. mm List Of Available Points W7761A Performance Specifications PowerEnvironmental Operating Temperature Specified Space Temperature Sensing RangeShipping Temperature Memory CapacityOutdoor Air Temperature Discharge Air TemperatureReturn Air Temperature Mixed Air Temperature5585 Wall ModulesT7780 construction, subbase dimensions in in. mm ConfigurationsOccupancy Sensor Mixed-Output-Type ControlWindow Open/Closed Digital Input Wall Module OptionsApplication Steps Step No Description OverviewPlan The System Bus Layout Lay Out Communications and Power WiringDetermine Other Bus Devices Required 750,1$ Power Budget Calculation Example Power WiringLine Loss VA Ratings For Transformer Sizing Device DescriptionNema class 2 transformer voltage output limits VA RatingLine VOLTAGE` GREATER` Than 150 VAC W7761A Devices Prepare Wiring DiagramsGeneral Considerations Terminal Number Description W7761A I/O DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Typical Pneumatic transducer Series 60 Floating to W7761A Bus Termination ModuleSee for E-Bus termination wiring options +$672 Excel 10 W7750 Controllers Order EquipmentT7770 Wall Modules SensorsEchelon Based Components and Parts AccessoriesCabling Temperature Degrees W7761A Device Status LED Broadcasting the Service MessageExcel 10 Alarms LED States T7780 Ddwm Bypass PushbuttonAdding Analog Inputs Enthalpy 4 to 20 mA Appendix A. Using E-Vision to Commission a W7761 DeviceAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Common Operations Room Temperature Sensor RmTempAppendix B. Sequences of Operation Dirty Filter Monitor Window Sensor StatusWndwSeries 60 Modulating Control Pulse Width Modulating PWM ControlRelative Temperature Relative HumidityAir Flow CO 2 ConcentrationTable C1. Input/Output Points Left DefaultTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left SH MA DA EV HW MN TS Table C2. Control Parameters RightTable C3. Status Points Left NoalarmTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Right Table C5. Direct Access And Special Points LeftFig. D-1. Point capacity estimate for Zone Manager Approximate Memory Size Estimating ProcedureResistance Sensors Appendix E. Sensor Data for CalibrationSensor Type Sensor Use1956.79 Humidity Percentage Sensor Voltage Voltage/Current SensorsTable E-4. Sensor Voltage Versus Humidity C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts Table E-10. Sensor Voltage Versus Input Voltage To A/D Table E-9. Sensor Voltage Versus CO 2 ConcentrationCO 2 Concentration PPM Sensor Voltage Pressure Inw kPa Sensor Voltage Vdc Voltage to A/D Sensor VoltageTable E-11. Sensor Voltage Vdc Versus Pressure Inw 3ODD