Honeywell W7761A specifications Valve Actuator

Page 29

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

 

 

 

 

PWM

 

 

 

 

 

 

 

 

 

 

 

VALVE ACTUATOR

 

 

 

 

 

 

 

 

 

ML7984B

 

PWM OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

24 (H)

24 (N) PWM (H 24 VAC)

FROM CNTRL

 

 

 

 

 

LINE POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T6

T5

C

B

W

R

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

24 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

CONTACTOR (24 VAC)

 

 

 

 

 

 

 

 

 

 

 

31

30

29

28

27

 

26

25

24

23

22

21

20

19

18

17

16

DI-4

GND

DI-3

DI-2

GND

 

DI-1

24 VAC

24 VAC COM

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

OUT 7

OUT 8

W7761A

 

 

 

 

 

TRIAC EQUIVALENT CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMOTE I/O

 

 

 

 

 

 

 

 

 

 

 

DEVICE

 

 

 

 

 

 

 

 

 

 

 

 

 

E GND

NOT USED

NOT USED

AI-1 OHM

GND

 

AI-2 OHM

AI-3 OHM

GND

AI-4 OHM

AI-5 V/mA

GND

AI-6 V/mA

22 VDC OUT

E-BUS

E-BUS JACK

 

 

 

1

2

3

4

5

 

6

7

8

9

10

11

12

13

14

15

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E-BUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.

2TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.

M15279

Fig. 19. Typical PWM Valve Actuator and miscellaneous fan control to W7761A. (For note 2, refer to Fig. 15.)

29

74-2699

Image 29
Contents Excel 10 W7761A Remote Input/Output Device Appendices List of TablesTypical system overview Description of DevicesControl Provided Control ApplicationProducts Covered Organization of ManualProduct Names Abbreviations and Definitions Agency ListingsExcel 10 W7761A INPUT/OUTPUT Device Controllers ConstructionExcel 10 W7761A Remote I/O Device W7761A construction in in. mm List Of Available Points W7761A Performance Specifications PowerEnvironmental Operating Temperature Specified Space Temperature Sensing RangeShipping Temperature Memory CapacityOutdoor Air Temperature Discharge Air TemperatureReturn Air Temperature Mixed Air Temperature5585 Wall ModulesT7780 construction, subbase dimensions in in. mm ConfigurationsOccupancy Sensor Mixed-Output-Type ControlWindow Open/Closed Digital Input Wall Module OptionsApplication Steps Step No Description OverviewPlan The System Bus Layout Lay Out Communications and Power WiringDetermine Other Bus Devices Required 750,1$ Power Budget Calculation Example Power WiringLine Loss VA Ratings For Transformer Sizing Device DescriptionNema class 2 transformer voltage output limits VA RatingLine VOLTAGE` GREATER` Than 150 VAC W7761A Devices Prepare Wiring DiagramsGeneral Considerations Terminal Number Description W7761A I/O DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Typical Pneumatic transducer Series 60 Floating to W7761A Bus Termination ModuleSee for E-Bus termination wiring options +$672 Excel 10 W7750 Controllers Order EquipmentT7770 Wall Modules SensorsEchelon Based Components and Parts AccessoriesCabling Temperature Degrees W7761A Device Status LED Broadcasting the Service MessageExcel 10 Alarms LED States T7780 Ddwm Bypass PushbuttonAdding Analog Inputs Enthalpy 4 to 20 mA Appendix A. Using E-Vision to Commission a W7761 DeviceAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Common Operations Room Temperature Sensor RmTempAppendix B. Sequences of Operation Dirty Filter Monitor Window Sensor StatusWndwSeries 60 Modulating Control Pulse Width Modulating PWM ControlRelative Temperature Relative HumidityAir Flow CO 2 ConcentrationTable C1. Input/Output Points Left DefaultTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left SH MA DA EV HW MN TS Table C2. Control Parameters RightTable C3. Status Points Left NoalarmTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Right Table C5. Direct Access And Special Points LeftFig. D-1. Point capacity estimate for Zone Manager Approximate Memory Size Estimating ProcedureResistance Sensors Appendix E. Sensor Data for CalibrationSensor Type Sensor Use1956.79 Humidity Percentage Sensor Voltage Voltage/Current SensorsTable E-4. Sensor Voltage Versus Humidity C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts Table E-10. Sensor Voltage Versus Input Voltage To A/D Table E-9. Sensor Voltage Versus CO 2 ConcentrationCO 2 Concentration PPM Sensor Voltage Pressure Inw kPa Sensor Voltage Vdc Voltage to A/D Sensor VoltageTable E-11. Sensor Voltage Vdc Versus Pressure Inw 3ODD