EXCEL 10 W7761A INPUT/OUTPUT DEVICE
|
|
|
| PWM |
|
|
|
|
|
|
|
|
| |||
|
| VALVE ACTUATOR |
|
|
|
|
|
|
| |||||||
|
| ML7984B |
| PWM OUTPUT |
|
|
|
|
|
|
|
|
|
|
| |
|
| 24 (H) | 24 (N) PWM (H 24 VAC) | FROM CNTRL |
|
|
|
|
| LINE POWER |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
| T6 | T5 | C | B | W | R |
|
|
|
|
|
|
|
| |
| + |
|
|
|
|
|
|
|
|
|
|
|
|
|
| FAN |
24 VAC |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| - |
|
|
|
|
|
|
|
|
| CONTACTOR (24 VAC) | |||||
|
|
|
|
|
|
|
|
|
|
| ||||||
31 | 30 | 29 | 28 | 27 |
| 26 | 25 | 24 | 23 | 22 | 21 | 20 | 19 | 18 | 17 | 16 |
GND | GND |
| 24 VAC | 24 VAC COM | OUT 1 | OUT 2 | OUT 3 | OUT 4 | OUT 5 | OUT 6 | OUT 7 | OUT 8 | ||||
W7761A |
|
|
|
|
| TRIAC EQUIVALENT CIRCUIT |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
REMOTE I/O |
|
|
|
|
|
|
|
|
|
|
| |||||
DEVICE |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
E GND | NOT USED | NOT USED | GND |
| GND | GND | 22 VDC OUT | |||||||||
|
|
| ||||||||||||||
1 | 2 | 3 | 4 | 5 |
| 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | J3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 |
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.
2TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
M15279
Fig. 19. Typical PWM Valve Actuator and miscellaneous fan control to W7761A. (For note 2, refer to Fig. 15.)
29 |