EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Appendix C. Complete List of Excel 10 W7761A Remote I/O Device User Addresses.

C1. Input/Output Points.

C2. Control Parameters.

C3. Status Points.

C4. Configuration Parameters.

C5. Direct Access And Special Points.

Table C0 lists the applicable Engineering Units for the analog points found in the W7761A.

Table C0. Engineering Units For Analog Points.

 

English Units (Inch-Pound)

Standard International Units (SI)

 

 

 

 

 

Measured Item

Description

Abbreviation

Description

Abbreviation

 

 

 

 

 

Temperature

Degrees Fahrenheit

F

Degrees Celsius

C

 

 

 

 

 

Relative

Delta Degrees Fahrenheit

DDF

Degrees Kelvin

K

Temperature

 

 

 

 

 

 

 

 

 

Relative Humidity

Percent

%

Percent

%

 

 

 

 

 

Air Flow

Cubic Feet per Minute

CFM

Meters cubed per hour

m3h

 

 

 

 

 

CO2 Concentration

Parts Per Million

PPM

Parts Per Million

PPM

Enthalpy

British Thermal Units per Pound

btu/lb

kiloJoules/kilogram

kJ/kg

 

of Air

 

 

 

 

 

 

 

 

Differential

Inches of Water Column

inw

kiloPascal

kPa

Pressure

 

 

 

 

 

 

 

 

 

Tables C1 through C5 list all network variables associated with the W7761A Controller and the default User Address names. Table C1 lists the Network Variable Inputs and Outputs, which are stored in RAM memory. Table C2 lists the Control Parameters, which are the values stored in the controllers EEPROM memory.

NOTE: Table C2. User Addresses For W7761A Control Parameters. (Control Parameters are stored in EEPROM - limited to 10,000 writes. Do NOT use as outputs from Control Strategies, Time Programs, or Switching Tables. If these points are changed more than 10,000 times, irreversible hardware failure results).

Tables provides point attributes as follows:

Engineering

 

Units—

This field indicates the point valid range and displayed Engineering Unit. For digital points, the valid states

 

and the corresponding enumerated values are shown.

Default—

The value or state of the point on controller start-up.

Shareable— The point can be set up for data sharing in Command Multiple Points, Read Multiple Points, or Refer Excel 10 Points as either a data source or a destination.

Mappable—

The point can be converted into a C-Bus point used by C-Bus devices. A mappable point has a one-to-one

Direct

relationship with a C-Bus User Address.

 

Access—

The point is accessible through the Subsystem Points mechanism in XBS.

E-Vision

 

Monitor—

These points are viewable within the E-Vision Controller Monitoring on-line screen. PAR refers to control

Hardware

parameters that are set in the Application Selection dialog boxes in E-Vision.

 

Config—

These are points that involve controller I/O configuration. Any change to HW Config. points causes the

 

W7761A to perform an application reset; therefore, these points can only be modified off-line.

Manual—

These points are used to set the controller outputs when in manual mode. The W7761A is placed in manual

 

mode through a menu selection in the E-Vision Controller Monitor screen.

Fixable—

These input points can be set to a constant value in the E-Vision Controller Monitor screen.

NOTES:

1.Mapped points can be viewed and changed, if applicable, on C-Bus devices such as an XI581, XI582 and XI584 and on an XBS central and E-Vision.

2.All Excel 10 points, mappable, calibration, configuration and internal data sharing points, can be viewed and changed, as allowed, via Direct Access (DA) mode in the XBS subsystem menu or via XI584.

3.E-Vision - These points are displayed to the user and polled during the E-Vision monitor function. Monitor (M) indicates the point appears in the Software list box. Schematic (S) indicates the point is to be displayed on the schematic air handler diagram directly. Calibrate (C) - These points are calibratible and the calibration dialog (either the temperature or air flow dialog) is displayed. These points are displayed in a listbox by selection of the menu item Controller, Calibration. When the user double clicks on these points the calibration dialog is displayed. Parameter (P) - This information is displayed to the user in the Application Selection screens. These fields are read/write when offline and read only when online.

4.Manual - These points can be placed in the manual mode. When the user double clicks on these points the manual dialog is displayed, this contains radio buttons; one for Auto and one for Manual.

44

74-2699

Image 44
Contents Excel 10 W7761A Remote Input/Output Device List of Tables AppendicesDescription of Devices Typical system overviewControl Application Control ProvidedProducts Covered Organization of ManualProduct Names Agency Listings Abbreviations and DefinitionsExcel 10 W7761A INPUT/OUTPUT Device Construction ControllersExcel 10 W7761A Remote I/O Device W7761A construction in in. mm Performance Specifications Power List Of Available Points W7761ASpecified Space Temperature Sensing Range Environmental Operating TemperatureShipping Temperature Memory CapacityDischarge Air Temperature Outdoor Air TemperatureReturn Air Temperature Mixed Air TemperatureWall Modules 5585Configurations T7780 construction, subbase dimensions in in. mmMixed-Output-Type Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsApplication Steps Step No Description OverviewPlan The System Bus Layout Lay Out Communications and Power WiringDetermine Other Bus Devices Required 750,1$ Power Wiring Power Budget Calculation ExampleVA Ratings For Transformer Sizing Device Description Line LossVA Rating Nema class 2 transformer voltage output limitsLine VOLTAGE` GREATER` Than 150 VAC W7761A Devices Prepare Wiring DiagramsGeneral Considerations W7761A I/O Description Terminal Number DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Bus Termination Module Typical Pneumatic transducer Series 60 Floating to W7761ASee for E-Bus termination wiring options +$672 Order Equipment Excel 10 W7750 ControllersT7770 Wall Modules SensorsAccessories Echelon Based Components and PartsCabling Temperature Degrees W7761A Device Status LED Broadcasting the Service MessageExcel 10 Alarms T7780 Ddwm Bypass Pushbutton LED StatesAppendix A. Using E-Vision to Commission a W7761 Device Adding Analog Inputs Enthalpy 4 to 20 mAAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Common Operations Room Temperature Sensor RmTempAppendix B. Sequences of Operation Window Sensor StatusWndw Dirty Filter MonitorSeries 60 Modulating Control Pulse Width Modulating PWM ControlTemperature Relative Humidity RelativeAir Flow CO 2 ConcentrationDefault Table C1. Input/Output Points LeftTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left Table C2. Control Parameters Right SH MA DA EV HW MN TSNoalarm Table C3. Status Points LeftTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Left Table C5. Direct Access And Special Points RightApproximate Memory Size Estimating Procedure Fig. D-1. Point capacity estimate for Zone ManagerAppendix E. Sensor Data for Calibration Resistance SensorsSensor Type Sensor Use1956.79 Humidity Percentage Sensor Voltage Voltage/Current SensorsTable E-4. Sensor Voltage Versus Humidity C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts Table E-10. Sensor Voltage Versus Input Voltage To A/D Table E-9. Sensor Voltage Versus CO 2 ConcentrationCO 2 Concentration PPM Sensor Voltage Pressure Inw kPa Sensor Voltage Vdc Voltage to A/D Sensor VoltageTable E-11. Sensor Voltage Vdc Versus Pressure Inw 3ODD