EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Table C4. Configuration Parameters (Right Continued).

Share (SH), Map (MA), Direct Access (DA)

 

 

E-Vision (EV): Calibrate (C), Monitor (M),

 

 

 

 

Parameter (P), Schematic (S)

 

 

 

Hardware Configuration (HW),

 

 

 

 

Manual Point (MN), Test (TS)

 

 

 

 

 

 

 

 

 

 

 

 

SH

MA

 

DA

EV

HW

MN

 

TS

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M

X

 

 

 

AIUpperLimit: This is the high limit value or the highest value that will be displayed

 

 

 

 

 

 

 

 

 

for this sensor. This value must be between the AIOutputRLow and AIOutputRHigh

 

 

 

 

 

 

 

 

 

and higher than the value specified for AILowLimit.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaC: The default value of delta for all RIO sensor types is set to zero. With this

 

 

 

 

 

 

 

 

 

default value, the RIO will send the sensor values at the fastest rate of 2 seconds

 

 

 

 

 

 

 

 

 

update rate. However, if the user desires to reduce the network traffic or not receive

 

 

 

 

 

 

 

 

 

the noisy sensor values, a delta value can be specified. This value will force the RIO

 

 

 

 

 

 

 

 

 

to transmit the sensor value when the current value exceeds the last sent value by

 

 

 

 

 

 

 

 

 

the delta amount. RIO will also send the sensor value whenever the time of update

 

 

 

 

 

 

 

 

 

exceeds nciRioSendT. RIO will send the sensor value at the rate of nciRioSendT

 

 

 

 

 

 

 

 

 

regardless of delta change.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaCO2: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaH: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaP: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaT1: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaT2: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaT3: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaT4: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

M P

X

 

 

 

DeltaV: Refer to the description for DeltaC.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

X

 

 

 

DO1FlSpeed is how long it takes for the actuator motor to move one cycle of travel

 

 

 

 

 

 

 

 

 

from closed to open. This value would be required if DO1Type were configured to

 

 

 

 

 

 

 

 

 

either Float_Open or Float_Close.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

X

 

 

 

DO2FlSpeed is how long it takes for the actuator motor to move one cycle of travel

 

 

 

 

 

 

 

 

 

from closed to open. This value would be required if DO2Type were configured to

 

 

 

 

 

 

 

 

 

either Float_Open or Float_Close.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

X

 

 

 

DO3FlSpeed is how long it takes for the actuator motor to move one cycle of travel

 

 

 

 

 

 

 

 

 

from closed to open. This value would be required if DO3Type were configured to

 

 

 

 

 

 

 

 

 

either Float_Open or Float_Close.

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

X

 

 

 

DO4FlSpeed is how long it takes for the actuator motor to move one cycle of travel

 

 

 

 

 

 

 

 

 

from closed to open. This value would be required if DO4Type were configured to

 

 

 

 

 

 

 

 

 

either Float_Open or Float_Close.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(continued)

66

74-2699

Image 66
Contents Excel 10 W7761A Remote Input/Output Device List of Tables AppendicesDescription of Devices Typical system overviewProducts Covered Control ApplicationControl Provided Organization of ManualProduct Names Agency Listings Abbreviations and DefinitionsExcel 10 W7761A INPUT/OUTPUT Device Construction ControllersExcel 10 W7761A Remote I/O Device W7761A construction in in. mm Performance Specifications Power List Of Available Points W7761AShipping Temperature Specified Space Temperature Sensing RangeEnvironmental Operating Temperature Memory CapacityReturn Air Temperature Discharge Air TemperatureOutdoor Air Temperature Mixed Air TemperatureWall Modules 5585Configurations T7780 construction, subbase dimensions in in. mmWindow Open/Closed Digital Input Mixed-Output-Type ControlOccupancy Sensor Wall Module OptionsOverview Plan The SystemApplication Steps Step No Description Lay Out Communications and Power Wiring Determine Other Bus Devices RequiredBus Layout 750,1$ Power Wiring Power Budget Calculation ExampleVA Ratings For Transformer Sizing Device Description Line LossVA Rating Nema class 2 transformer voltage output limitsLine VOLTAGE` GREATER` Than 150 VAC Prepare Wiring Diagrams General ConsiderationsW7761A Devices W7761A I/O Description Terminal Number DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Bus Termination Module Typical Pneumatic transducer Series 60 Floating to W7761ASee for E-Bus termination wiring options +$672 T7770 Wall Modules Order EquipmentExcel 10 W7750 Controllers SensorsAccessories Echelon Based Components and PartsCabling Temperature Degrees Broadcasting the Service Message Excel 10 AlarmsW7761A Device Status LED T7780 Ddwm Bypass Pushbutton LED StatesAppendix A. Using E-Vision to Commission a W7761 Device Adding Analog Inputs Enthalpy 4 to 20 mAAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Room Temperature Sensor RmTemp Appendix B. Sequences of OperationCommon Operations Series 60 Modulating Control Window Sensor StatusWndwDirty Filter Monitor Pulse Width Modulating PWM ControlAir Flow Temperature Relative HumidityRelative CO 2 ConcentrationDefault Table C1. Input/Output Points LeftTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left Table C2. Control Parameters Right SH MA DA EV HW MN TSNoalarm Table C3. Status Points LeftTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Left Table C5. Direct Access And Special Points RightApproximate Memory Size Estimating Procedure Fig. D-1. Point capacity estimate for Zone ManagerSensor Type Appendix E. Sensor Data for CalibrationResistance Sensors Sensor Use1956.79 Voltage/Current Sensors Table E-4. Sensor Voltage Versus HumidityHumidity Percentage Sensor Voltage C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts Table E-9. Sensor Voltage Versus CO 2 Concentration CO 2 Concentration PPM Sensor VoltageTable E-10. Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Sensor Voltage Table E-11. Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc 3ODD