EXCEL 10 W7761A INPUT/OUTPUT DEVICE
The T7770A,B,C,D wall module is the room space temperature
Window Sensor (StatusWndw)
The digital input for a window contact can be wired into the W7761A device and then bound to a W7750 CVAHU to disable its temperature control algorithm if someone has opened a window or door in the room or area that the W7750 is serving. When a window is detected to be Open (digital input contacts Open equals window open), the normal temperature control is disabled, and the W7750 Controller enters the Freeze Protect mode. Freeze Protect mode sets the space setpoint to 50 °F (10°C) and brings on the fan and heat if the space temperature falls below this setpoint. Normal temperature control resumes on window closure.
Dirty Filter Monitor
The air filter in the air handler can be monitored by a digital input in the W7761A and an alarm issued by the Zone Manager when the filter media needs replacement. The two methods of monitoring the filter are:
1.A differential pressure switch whose contacts are connected to a digital input on the W7761A and;
2.A 2 to 10V differential pressure sensor wired to a voltage input on the W7761A. If the analog input sensor is used, its measured value 0 to 5 inw (0 to 1.25 kPa) is compared to a
Series 60 Modulating Control
Series 60 Control is also commonly referred to as Floating Control. The Excel 10 W7761A Device can drive Series 60 type actuators to control a modulating damper or valve actuator. The W7761A device contains no control software, so these outputs would have to be bound to either the Zone Manager or other Excel 10 controllers. When floating control is used, the
Pulse Width Modulating (PWM) Control
The Excel 10 W7761A device can drive a
Example: To find the pulse width of a valve actuator (for example stroke mid position - 50 percent) with the PWMZeroScale =
0.1seconds, PWMFullScale = 25.5 seconds, and the PWMPeriod = 25.6 seconds. There are 256 increments available, so the number of increments required for 50 percent would be (0.5 X 256) or 128. The time for each increment for this industry standard pulse time is 0.1 seconds. The pulse width is the minimum time (0.1 second) + the number of increments (128 times the seconds added 0.1) = 12.9 seconds. The W7750B Controller would command the valve output on for 12.9 seconds every
25.6seconds to maintain the valve position at 50 percent.
Indoor Air Quality (IAQ) Override
The Excel 10 W7761A Device can monitor an IAQ sensor and that input can be bound to a W7750 CVAHU Controller that supports an IAQ override feature, that upon detection of poor air quality in the space, allows the economizer dampers to be opened above the standard minimum position setting to a value set in EconIAQPos (parameter located in W7750). Two different methods of detecting poor air quality are supported, The first is by using an IAQ switch device connected to a digital input on the W7761A Device, where a contact closure indicates poor air quality. This digital input would then be bound to the W7750 Controller that is serving the area being monitored and would initiate the IAQ override mode. The second is through an analog input that connects to a CO2 Sensor (0 to 10V). The measured value of CO2 from this sensor (0 to 2000 ppm) is mapped into the Zone Manager where it is compared to a setpoint (parameter located in the Zone Manager). When the CO2 level is higher than the setpoint, the Zone Manager can initiate an IAQ alarm. A pseudo digital point in the Zone Manager can be bound to the W7750 CVAHU Controller which can initiate the IAQ override mode.
43 |