Honeywell W7761A specifications Approximate Memory Size Estimating Procedure

Page 71

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Appendix D. Q7750A Excel 10

Zone Manager Point Estimating Guide.

Memory size approximation is shown below: (all sizes in bytes)

When memory size is less than 110,000 bytes, the size is OK.

When memory size is between 110,000 and 128,000 bytes, the application may be too large. The user must expect to reduce the application complexity, reduce the number of attached Excel 10s or distribute the Excel 10s over more than one Zone Manager.

When memory size is greater than 128,000, the size is too large. The application size must be reduced as described above.

Approximate Memory Size Estimating Procedure.

1.Determine the number of points per controller required at the Central (for example, XBS).

NOTE: All remaining points that are not mapped can be accessed through the Direct Access feature.

2.Calculate the number of Excel 10 Zone Manager program points that are used in control logic and in the switching table.

3.Estimate the program complexity of the Zone Manager (one of three levels).

a.No time programs, control logic, or switching tables.

b.10K of control logic (one time program, five switching tables, and five control loops).

c.20K of control logic (multiple time programs, ten switching tables, and ten control loops).

Use Fig. D-1 to determine the number of Excel 10s that can be connected to the Zone Manager. NOTE: More than 60 Excel 10s requires a Router.

4. Repeat for each Q7750A Excel 10 Zone Manager in a project.

 

920

 

900

 

800

NUMBER OF

765

C-BUS POINTS (EXCEL 10 MAPPED

POINTS

700

PLUS ZONE

 

MANAGER

 

POINTS)

 

610

600

(A)NO TIME PROGRAM, NO CONTROL LOOPS, NO SWITCHING TABLES.

(B)10K CONTROL PROGRAM (I.E., 1 TIME PROGRAM, 5 CONTROL LOOPS,

5 SWITCHING TABLES.)

(C)20K CONTROL PROGRAM

(I.E., MULTIPLE TIME PROGRAMS, 10 CONTROL LOOPS,

10 SWITCHING TABLES.)

900

895

800

NUMBER OF

740C-BUS POINTS (EXCEL 10

MAPPED

700POINTS PLUS ZONE MANAGER POINTS)

600

585

20

60

(OR LESS)

(ADD ROUTER)

120

NUMBER OF EXCEL 10s

 

M8729

 

Fig. D-1. Point capacity estimate for Zone Manager.

The exact equation for calculating memory size follows:

Memory size = 21,780

+4096 (in case of a time program).

+CARE Control Program.

+14 x time points x Excel 10 units.

+50 x Excel 10 units.

+map complexity x Excel 10 units x mapped points.

+57 x C-Bus points.

+7488 x Excel 10 types.

Where:

 

Time points

= number of switch points in time program per Excel 10.

Excel 10 units

= number of attached Excel 10s.

C-Bus points

= including mapped points and others; for example, remote points.

Mapped points

= number of mapped points per Excel 10,

 

including One-to-Many and Many-to-One

 

mechanism.

Excel 10 types

= number of different Excel 10 types (currently three)

Map complexity

=

20

= using One-to-Many and not using

 

points with read/write.

30

= average.

45

= many points with read/write ability.

71

74-2699

Image 71
Contents Excel 10 W7761A Remote Input/Output Device Appendices List of TablesTypical system overview Description of DevicesOrganization of Manual Control ApplicationControl Provided Products CoveredProduct Names Abbreviations and Definitions Agency ListingsExcel 10 W7761A INPUT/OUTPUT Device Controllers ConstructionExcel 10 W7761A Remote I/O Device W7761A construction in in. mm List Of Available Points W7761A Performance Specifications PowerMemory Capacity Specified Space Temperature Sensing RangeEnvironmental Operating Temperature Shipping TemperatureMixed Air Temperature Discharge Air TemperatureOutdoor Air Temperature Return Air Temperature5585 Wall ModulesT7780 construction, subbase dimensions in in. mm ConfigurationsWall Module Options Mixed-Output-Type ControlOccupancy Sensor Window Open/Closed Digital InputApplication Steps Step No Description OverviewPlan The System Bus Layout Lay Out Communications and Power WiringDetermine Other Bus Devices Required 750,1$ Power Budget Calculation Example Power WiringLine Loss VA Ratings For Transformer Sizing Device DescriptionNema class 2 transformer voltage output limits VA RatingLine VOLTAGE` GREATER` Than 150 VAC W7761A Devices Prepare Wiring DiagramsGeneral Considerations Terminal Number Description W7761A I/O DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Typical Pneumatic transducer Series 60 Floating to W7761A Bus Termination ModuleSee for E-Bus termination wiring options +$672 Sensors Order EquipmentExcel 10 W7750 Controllers T7770 Wall ModulesEchelon Based Components and Parts AccessoriesCabling Temperature Degrees W7761A Device Status LED Broadcasting the Service MessageExcel 10 Alarms LED States T7780 Ddwm Bypass PushbuttonAdding Analog Inputs Enthalpy 4 to 20 mA Appendix A. Using E-Vision to Commission a W7761 DeviceAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Common Operations Room Temperature Sensor RmTempAppendix B. Sequences of Operation Pulse Width Modulating PWM Control Window Sensor StatusWndwDirty Filter Monitor Series 60 Modulating ControlCO 2 Concentration Temperature Relative HumidityRelative Air FlowTable C1. Input/Output Points Left DefaultTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left SH MA DA EV HW MN TS Table C2. Control Parameters RightTable C3. Status Points Left NoalarmTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Right Table C5. Direct Access And Special Points LeftFig. D-1. Point capacity estimate for Zone Manager Approximate Memory Size Estimating ProcedureSensor Use Appendix E. Sensor Data for CalibrationResistance Sensors Sensor Type1956.79 Humidity Percentage Sensor Voltage Voltage/Current SensorsTable E-4. Sensor Voltage Versus Humidity C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts Table E-10. Sensor Voltage Versus Input Voltage To A/D Table E-9. Sensor Voltage Versus CO 2 ConcentrationCO 2 Concentration PPM Sensor Voltage Pressure Inw kPa Sensor Voltage Vdc Voltage to A/D Sensor VoltageTable E-11. Sensor Voltage Vdc Versus Pressure Inw 3ODD