EXCEL 10 W7761A INPUT/OUTPUT DEVICE
displayed. Select the project and the Zone manager within that project that is being exported and the Export button. Exit CARE and Start
4.Select the Controller menu item and then Import from CARE to import the Zone Manager files with the new pseudo analog point. If this function has already been performed before, the user will be prompted with the message CARE Export File has already been imported, do you want to import again?. Select Yes to continue with the Import. When the import is finished,
5.Select the Network menu item and then Map
6.
7.Select the Controller menu item and the Update Zone Manager Files.
8.Start CARE and open the Zone Manager that was just updated through the Update Zone Manager Files function and start XI584 by selecting the Controller, Tools and XI584 menu items. Once XI584 is started, select the Utilities, File Transfer menu items and select CARE Import. Select the project and the Zone Manager that was just updated and select Import and click OK on the Select Target Controller dialog box. When the CARE Import is complete, close the CARE Import dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set by the XI581 Emulation function (Applications, XI581 Emulation menu). Select the Utilities, File Transfer menu items and select Download. The Download dialog box will be displayed. Check the All selection and click the Controller button. When the Select Controller/Subsystem dialog box is displayed, make sure that the correct CPU address or name is highlighted and select the OK button. Click the Download button and Yes to the message Replace updated application part in controller (CPU address or Controller name). When the download is complete, exit out of the Download dialog box. From the XI584 main menu, select the Data, Access by User Address menu items. Type MiscExhFan in the Search For User Address and click on the Search button. When the MiscExhFan point displays in the User Addresses list, click on the point and select the Attributes button. XI584 will now display the value of the Digital Output connected to the RIO device. To command the MiscExhFan to the On mode, put the point in the Manual mode and enter a value of 1.0 or greater. To command the MiscExhFan to the Off mode, put the point in the Manual mode and enter a value of 0.0. This point can now be used in the Zone Manager control strategy or switching logic and Time Programs. This point can be used in other Excel 5000 controllers
Table
RIO Network Variable that contains the | |
Application Selection Tab | Hardware Output Value |
|
|
Float1_Open through Float8_Open (Series 60 - | DigOut1Cmd through DigOut8Cmd |
requires two outputs assigned. Float1_Open |
|
must be assigned before Float1_Close) |
|
|
|
Float1_Close through Float8_Close (Series 60 | DigOut1Cmd through DigOut8Cmd |
- requires two outputs assigned. Float1_Open |
|
must be assigned before Float1_Close) |
|
|
|
Discrete1 through Discrete8 (Maintained On/Off | DigOut1Cmd through DigOut8Cmd |
outputs) |
|
|
|
Modulate1 through Modulate8 (PWM outputs) | DigOut1Cmd through DigOut8Cmd |
|
|
Appendix B. Sequences of Operation.
Common Operations
The Excel 10 W7761A Device contains inputs and outputs, but no control software. All control that would be associated with the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for VAV control, temperature control, or any control function that would require less than a 30 second update rate. The analog and digital sensors could be shared or bound to other Excel 10 controllers on the
Room Temperature Sensor (RmTemp)
42 |