Honeywell W7761A Memory Capacity, Specified Space Temperature Sensing Range, Communications

Page 12

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

CPU:

Motorola or Toshiba 3150 Neuronprocessor, containing three eight-bit CPU’s. Each Neuronhas a unique 48-bit network identification number.

Memory Capacity:

64K ROM/PROM (6K reserved for network operations, 58K usable for control algorithm code). 512 bytes EEPROM.

2K RAM.

Specified Space Temperature Sensing Range:

45 to 99°F (7 to 37°C) with an allowable control setpoint range from 50 to 90°F (10 to 32°C) when initiated from the network and 55 to 85°F (13 to 29°C) when configured and connected to T7770 Wall Modules or T7780 DDWM.

Communications:

The W7761A Device uses a transformer-coupled communications port with differential Manchester-encoded data at 78 kilobits per second (kbs). The transformer-coupled communications interface offers a much higher degree of common-mode noise rejection while ensuring dc isolation.

Approved cable types for E-Bus communications wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated unshielded, twisted pair, solid conductor wire. For non-plenum areas, use Level IV 22 AWG (0.34 mm2) such as U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm2) such as U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). (See Tables 6 and 8 for part numbers.) Contact Echelon® Corp. Technical Support for the recommended vendors of Echelon® approved cables.

The Free Topology Transceiver (FTT) supports polarity insensitive free topology wiring. This frees the system installer from the need to wire using a bus topology. Star, bus, mixed, and loop wiring are all supported by this architecture. The maximum E-Bus length when using a combination of star, loop, and bus wiring (singly terminated) is 1640 ft (500m) with the maximum node-to- node length of 1312 ft (400m). In the event that the total wire length is exceeded, then a Q7740A 2-Way Repeater or a Q7740B 4-Way Repeater can be used to allow the number of devices to be spread out as well as increasing the length of wire over which they communicate. The maximum number of repeaters per segment is one (on either side of the router). A Q7751A E- Bus Router can also be used to effectively double the maximum E-Bus length. The advantage of using the router is that it will segregate traffic to a segment while when using the repeater, all traffic is repeated on each segment. When utilizing a doubly terminated E-Bus structure, use a continuous daisy-chain with no stubs or taps from the main backbone, The maximum E-Bus length is 4593 ft (1400m) with the maximum node-to-node length of 3773 ft (1150m).

FTT networks are very flexible and convenient to install and maintain, but it is imperative to carefully plan the network layout and create and maintain accurate documentation. Unknown or inaccurate wire run lengths, node-to-node distances, node counts, total wire length, and misplaced or missing terminators can cause poor network performance. Refer to E-Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules.

LonMark® Functional Profile

W7761A Device supports the LonMark® Preliminary Functional Profile for a Remote Input/Output Device.

Environmental:

Operating Temperature:

-40° to 150°F (-40° to 65.5°C).

Shipping Temperature:

-40° to 150°F (-40° to 65.5°C).

Relative Humidity:

5% to 95% noncondensing.

Vibration:

Rated V2 level compliant.

Inputs/Outputs:

The W7761A Unit supports the following hardware features:

Four 20KNTC (1000 through 150,000 ohm) or PT3000 (250 through 12,000 ohm) resistive analog inputs.

Two 0.2 to 10 VDC or 2 to 20 mA (user selectable) analog inputs.

Four dry contact digital inputs.

Eight 24 Vac Triac digital outputs (500 mA MAX).

One 22 Vdc power supply for auxiliary devices with a maximum current of 50 mA.

Analog Inputs:

Space Temperature:

Type: RTD.

12

74-2699

Image 12
Contents Excel 10 W7761A Remote Input/Output Device List of Tables AppendicesDescription of Devices Typical system overviewControl Application Control ProvidedProducts Covered Organization of ManualProduct Names Agency Listings Abbreviations and DefinitionsExcel 10 W7761A INPUT/OUTPUT Device Construction ControllersExcel 10 W7761A Remote I/O Device W7761A construction in in. mm Performance Specifications Power List Of Available Points W7761ASpecified Space Temperature Sensing Range Environmental Operating TemperatureShipping Temperature Memory CapacityDischarge Air Temperature Outdoor Air TemperatureReturn Air Temperature Mixed Air TemperatureWall Modules 5585Configurations T7780 construction, subbase dimensions in in. mmMixed-Output-Type Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsOverview Plan The SystemApplication Steps Step No Description Lay Out Communications and Power Wiring Determine Other Bus Devices RequiredBus Layout 750,1$ Power Wiring Power Budget Calculation ExampleVA Ratings For Transformer Sizing Device Description Line LossVA Rating Nema class 2 transformer voltage output limitsLine VOLTAGE` GREATER` Than 150 VAC Prepare Wiring Diagrams General ConsiderationsW7761A Devices W7761A I/O Description Terminal Number DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Bus Termination Module Typical Pneumatic transducer Series 60 Floating to W7761ASee for E-Bus termination wiring options +$672 Order Equipment Excel 10 W7750 ControllersT7770 Wall Modules SensorsAccessories Echelon Based Components and PartsCabling Temperature Degrees Broadcasting the Service Message Excel 10 AlarmsW7761A Device Status LED T7780 Ddwm Bypass Pushbutton LED StatesAppendix A. Using E-Vision to Commission a W7761 Device Adding Analog Inputs Enthalpy 4 to 20 mAAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Room Temperature Sensor RmTemp Appendix B. Sequences of OperationCommon Operations Window Sensor StatusWndw Dirty Filter MonitorSeries 60 Modulating Control Pulse Width Modulating PWM ControlTemperature Relative Humidity RelativeAir Flow CO 2 ConcentrationDefault Table C1. Input/Output Points LeftTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left Table C2. Control Parameters Right SH MA DA EV HW MN TSNoalarm Table C3. Status Points LeftTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Left Table C5. Direct Access And Special Points RightApproximate Memory Size Estimating Procedure Fig. D-1. Point capacity estimate for Zone ManagerAppendix E. Sensor Data for Calibration Resistance SensorsSensor Type Sensor Use1956.79 Voltage/Current Sensors Table E-4. Sensor Voltage Versus HumidityHumidity Percentage Sensor Voltage C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts Table E-9. Sensor Voltage Versus CO 2 Concentration CO 2 Concentration PPM Sensor VoltageTable E-10. Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Sensor Voltage Table E-11. Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc 3ODD