EXCEL 10 W7761A INPUT/OUTPUT DEVICE

average many space temperature sensors that are located in a zone that is controlled by the W7750 Constant Volume AHU Controller.

Mixed-Output-Type Control

The W7761A Device can control mixed-output-types of applications such as PWM and staged control occurring simultaneously with Series 60 Floating Control.

Occupancy Sensor

Excel 10 W7761A device can be connected to an occupancy sensor through a digital input. This is a device, such as a passive infrared motion detector, that contains a dry contact (see following NOTE) closure to indicate whether or not people are present in the space. The Excel 10 W7761A Device expects a contact closure to indicate the space is Occupied. See Fig. 18 in Application Step 4, Prepare Wiring Diagrams, for details on wiring connections. This occupancy sensor can then be bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. This would allow the other Excel 10 controllers to use their physical inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control.

NOTE: The Excel 10 Controllers (W7750 CVAHU and W7761A RIO) have limited power available (only 9 mA at 4.8 volts) for checking the digital inputs for contact closures. It is very important that the device used contains high quality, noncorroding contacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as gold or silver), pimpled or sealed contacts to assure consistent, long-term operation.

The recommended devices for use with the Excel 10 W7750 Controller and W7761A Device are the EL7628A1007 Ceiling Mounted Infrared or the EL7680A1008 Wall Mounted Wide View Infrared Occupancy Sensors. If ultrasonic sensors are required, the EL7611A1003 and the EL7612A1001 Occupancy Sensors are recommended. An EL76XX Power Supply/Control Unit is required for use with these occupancy sensors. The EL7630A1003 can power up to four sensors, and is multi-tapped for several line voltages. The EL7621A1002 can power three sensors and it connects to 120 Vac line voltage. The EL7621A1010 can also power three sensors but it connects to 277 Vac line voltage.

Window Open/Closed Digital Input

Excel 10 W7761A device can be connected to a window sensor to indicate whether a window in the space was opened. The Excel 10 W7761A device can be connected to a dry contact (see the NOTE for the Occupancy Sensor and Fig. 18 in Application Step 4. Prepare Wiring Diagrams, for details) or a set of contacts wired in series (for monitoring multiple windows) to verify that the window(s) are closed. This window(s) sensor can then be bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. The algorithm in the other Excel 10 controllers expects a contact closure to indicate the window is closed. If an open window is detected, the algorithm in the other Excel 10 controllers changes the mode of operation to FREEZE_PROTECT, which shuts down the control functions, and watches for low space temperature conditions. The freeze protection setpoint is 46.4°F (8°C), and the frost alarm occurs at 42.8°F (6°C).

Wall Module Options

As previously discussed, there are five basic varieties of the T7770. There is one variety of the PT3000 sensor and the T7780 DDWM (see the Product Names and the Construction sections). The T7770A,B,C,D 20Kohm NTC sensor—(current feature that can be used with the RIO Device) and one PT3000 sensor can be configured on any of the four resistive inputs. The T7780 is an E-Bus node and would not be directly connected to the RIO Device.

Dirty Filter Monitor

The air filter in the air handler can be monitored by the W7761A RIO device and an alarm issued by the Zone Manager when the filter media needs replacement. The two methods of monitoring the filter are:

1.Connecting a differential pressure switch to a digital input on the W7761A.

2.Wiring a 2-to-10V differential pressure sensor to a voltage input on the W7761A. If the analog input sensor is used, its measured value 0 to 5 inw (0 to 1.25 kPa) is compared to a user-selectable setpoint. The comparison is done in the Zone Manager —valid range: 0 to 5 inw (0 to 1.25 kPa), and the Dirty Filter alarm is issued when the pressure drop across the filter exceeds the setpoint.

Indoor Air Quality (IAQ)

The Excel 10 W7761A device can monitor IAQ using one of two different methods of detecting poor air quality. The first is with an IAQ switch device connected to a digital input on the W7761A, where a contact closure indicates poor air quality, and an alarm can be issued by the Zone Manager. The device can detect poor air quality using any desired measure such as CO2, VOC, CO, etc. The second method, is through an analog input that connects to a CO2 sensor (0 to 10V). The measured value of CO2 from this sensor (0 to 2000 ppm) is compared to a user-selectable setpoint (the comparison is done in the Zone Manager —valid range: 0 to 2000 ppm), and an IAQ alarm can be issued when the CO 2 level exceeds the setpoint. The IAQ sensor that is connected to the W7750 RIO, can be bound to other W7750 CVAHU Excel 10 controllers on the E-Bus.

16

74-2699

Image 16
Contents Excel 10 W7761A Remote Input/Output Device List of Tables AppendicesDescription of Devices Typical system overviewControl Application Control ProvidedProducts Covered Organization of ManualProduct Names Agency Listings Abbreviations and DefinitionsExcel 10 W7761A INPUT/OUTPUT Device Construction ControllersExcel 10 W7761A Remote I/O Device W7761A construction in in. mm Performance Specifications Power List Of Available Points W7761ASpecified Space Temperature Sensing Range Environmental Operating TemperatureShipping Temperature Memory CapacityDischarge Air Temperature Outdoor Air TemperatureReturn Air Temperature Mixed Air TemperatureWall Modules 5585Configurations T7780 construction, subbase dimensions in in. mmMixed-Output-Type Control Occupancy SensorWindow Open/Closed Digital Input Wall Module OptionsPlan The System OverviewApplication Steps Step No Description Determine Other Bus Devices Required Lay Out Communications and Power WiringBus Layout 750,1$ Power Wiring Power Budget Calculation ExampleVA Ratings For Transformer Sizing Device Description Line LossVA Rating Nema class 2 transformer voltage output limitsLine VOLTAGE` GREATER` Than 150 VAC General Considerations Prepare Wiring DiagramsW7761A Devices W7761A I/O Description Terminal Number DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Bus Termination Module Typical Pneumatic transducer Series 60 Floating to W7761ASee for E-Bus termination wiring options +$672 Order Equipment Excel 10 W7750 ControllersT7770 Wall Modules SensorsAccessories Echelon Based Components and PartsCabling Temperature Degrees Excel 10 Alarms Broadcasting the Service MessageW7761A Device Status LED T7780 Ddwm Bypass Pushbutton LED StatesAppendix A. Using E-Vision to Commission a W7761 Device Adding Analog Inputs Enthalpy 4 to 20 mAAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Appendix B. Sequences of Operation Room Temperature Sensor RmTempCommon Operations Window Sensor StatusWndw Dirty Filter MonitorSeries 60 Modulating Control Pulse Width Modulating PWM ControlTemperature Relative Humidity RelativeAir Flow CO 2 ConcentrationDefault Table C1. Input/Output Points LeftTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left Table C2. Control Parameters Right SH MA DA EV HW MN TSNoalarm Table C3. Status Points LeftTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Left Table C5. Direct Access And Special Points RightApproximate Memory Size Estimating Procedure Fig. D-1. Point capacity estimate for Zone ManagerAppendix E. Sensor Data for Calibration Resistance SensorsSensor Type Sensor Use1956.79 Table E-4. Sensor Voltage Versus Humidity Voltage/Current SensorsHumidity Percentage Sensor Voltage C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts CO 2 Concentration PPM Sensor Voltage Table E-9. Sensor Voltage Versus CO 2 ConcentrationTable E-10. Sensor Voltage Versus Input Voltage To A/D Table E-11. Sensor Voltage Vdc Versus Pressure Inw Voltage to A/D Sensor VoltagePressure Inw kPa Sensor Voltage Vdc 3ODD