Honeywell W7761A specifications VA Ratings For Transformer Sizing Device Description, Line Loss

Page 21

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

ML6161

2.2 VA

TRADELINE®

Damper Actuator

 

Catalog

R8242A

21.0 VA

TRADELINE®

Contactor for fan

 

Catalog in-rush rating

M6410A Steam

0.7 VA

TRADELINE®

Heating Coil Valve

 

Catalog, 0.32A at 24 Vac

TOTAL: 29.9 VA

The Excel 10 System example requires 29.9 VA of peak power; therefore, a 40 VA AT72D Transformer is able to provide ample power for this device and its accessories. Alternatively, a 75 VA AT88A Transformer could be used to power two Excel 10 Systems of this type, or a 100 VA AT92A Transformer could be used to power three of these controllers and meet NEC Class 2 restrictions (no greater than 100 VA). See Fig. 12 through 14 for illustrations of power wiring details. See Table 5 for VA ratings of various devices.

Table 5 . VA Ratings For Transformer Sizing.

Device

Description

VA

 

 

 

W7761A

Excel 10 W7761 Device

6.0

 

 

 

ML6161A/B

Damper Actuator, 35 lb-in.

2.2

 

 

 

R8242A

Contactor

21.0

 

 

 

R6410A

Valve Actuator

0.7

 

 

 

MMC325

Pneumatic Transducer

5.0

 

 

 

ML684

Versadrive Valve Actuator

12.0

 

 

 

ML6464

Damper Actuator, 66 lb-in.

3.0

 

 

 

ML6474

Damper Actuator, 132 lb-in.

3.0

 

 

 

ML6185

Damper Actuator SR 50 lb-in.

12.0

 

 

 

For contactors and similar devices, the in-rush power ratings should be used as the worst case values when performing power budget calculations. Also, the application engineer must consider the possible combinations of simultaneously energized outputs and calculate the VA ratings accordingly. The worst case, that uses the largest possible VA load, should be determined when sizing the transformer.

Line Loss

Excel 10 Controllers must receive a minimum supply voltage of 20 Vac. If long power or output wire runs are required, a voltage drop due to Ohms Law (I x R) line loss must be considered. This line loss can result in a significant increase in total power required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft (61m) run from the transformer to a W7761 Device drawing 37 VA using 18 AWG (1.0 mm2) wire.

The formula is:

Loss = [length of round-trip wire run (ft)] x [resistance in wire (ohms per ft)] x [current in wire (amperes)] From specification data:

18 AWG twisted pair wire has 6.52 ohms per 1000 feet.

Loss = [(200 ft) x (2 - round-trip) x (6.52/1000 ohms per ft)] x [(37 VA)/(24V)] = 4.02 volts

This means that four volts are going to be lost between the transformer and the device; therefore, to assure the device receives at least 20 volts, the transformer must output more than 24 volts. Because all transformer output voltage levels depend on the size of the connected load, a larger transformer outputs a higher voltage than a smaller one for a given load. Fig. 11 shows this voltage load dependence.

In the preceding I x R loss example, even though the device load is only 37 VA, a standard 40 VA transformer is not sufficient due to the line loss. From Fig. 11, a 40 VA transformer is just under 100 percent loaded (for the 37 VA device) and, therefore, has a secondary voltage of 22.9 volts. (Use the lower edge of the shaded zone in Fig. 11 that represents the worst case conditions.) When the I x R loss of four volts is subtracted, only 18.9 volts reaches the device, which is not enough voltage for proper operation.

In this situation, the engineer basically has three alternatives:

1.Use a larger transformer; for example, if an 80 VA model is used, see Fig. 11, an output of 24.4 volts minus the four volt line loss supplies 20.4V to the device. Although acceptable, the four-volt line-loss in this example is higher than recommended. See the following IMPORTANT.

2.Use heavier gauge wire for the power run. 14 AWG (2.0 mm2) wire has a resistance of 2.57 ohms per 1000 ft which,

using the preceding formula, gives a line-loss of only 1.58 volts (compared with 4.02 volts). This would allow a 40 VA transformer to be used. 14 AWG (2.0 mm2) wire is the recommended wire size for 24 Vac wiring.

3.Locate the transformer closer to the device, thereby reducing the length of the wire run, and the line loss.

The issue of line-loss is also important in the case of the output wiring connected to the Triac digital outputs. The same formula and method are used. The rule to remember is to keep all power and output wire runs as short as practical. When necessary, use heavier gauge wire, a bigger transformer, or install the transformer closer to the device.

IMPORTANT

21

74-2699

Image 21
Contents Excel 10 W7761A Remote Input/Output Device Appendices List of TablesTypical system overview Description of DevicesControl Provided Control ApplicationProducts Covered Organization of ManualProduct Names Abbreviations and Definitions Agency ListingsExcel 10 W7761A INPUT/OUTPUT Device Controllers ConstructionExcel 10 W7761A Remote I/O Device W7761A construction in in. mm List Of Available Points W7761A Performance Specifications PowerEnvironmental Operating Temperature Specified Space Temperature Sensing RangeShipping Temperature Memory CapacityOutdoor Air Temperature Discharge Air TemperatureReturn Air Temperature Mixed Air Temperature5585 Wall ModulesT7780 construction, subbase dimensions in in. mm ConfigurationsOccupancy Sensor Mixed-Output-Type ControlWindow Open/Closed Digital Input Wall Module OptionsOverview Plan The SystemApplication Steps Step No Description Lay Out Communications and Power Wiring Determine Other Bus Devices RequiredBus Layout 750,1$ Power Budget Calculation Example Power WiringLine Loss VA Ratings For Transformer Sizing Device DescriptionNema class 2 transformer voltage output limits VA RatingLine VOLTAGE` GREATER` Than 150 VAC Prepare Wiring Diagrams General ConsiderationsW7761A Devices Terminal Number Description W7761A I/O DescriptionTemperature Sensor DE V IC E Window Contact Contact Closed = Occupancy Sensor Occupied Valve Actuator Typical Pneumatic transducer Series 60 Floating to W7761A Bus Termination ModuleSee for E-Bus termination wiring options +$672 Excel 10 W7750 Controllers Order EquipmentT7770 Wall Modules SensorsEchelon Based Components and Parts AccessoriesCabling Temperature Degrees Broadcasting the Service Message Excel 10 AlarmsW7761A Device Status LED LED States T7780 Ddwm Bypass PushbuttonAdding Analog Inputs Enthalpy 4 to 20 mA Appendix A. Using E-Vision to Commission a W7761 DeviceAdding Other VOLTAGE/CURRENT Sensors Adding Digital Inputs Room Temperature Sensor RmTemp Appendix B. Sequences of OperationCommon Operations Dirty Filter Monitor Window Sensor StatusWndwSeries 60 Modulating Control Pulse Width Modulating PWM ControlRelative Temperature Relative HumidityAir Flow CO 2 ConcentrationTable C1. Input/Output Points Left DefaultTable C1. Input/Output Points Right Excel 10 W7761A INPUT/OUTPUT Device Values that can be assigned to any output channels English Metric or User Address DI3Sel1Type Refer to the description for DI1Sel1Type Stoff Stnul Stlow Stmed Sthigh Ston DO2Type Excel 10 W7761A INPUT/OUTPUT Device SrcDigIn2Sts Refer to the description for SrcDigIn1Sts Table C2. Control Parameters Left SH MA DA EV HW MN TS Table C2. Control Parameters RightTable C3. Status Points Left NoalarmTable C3. Status Points Right RIO1 Software version NvoStatus InOverride SH MA DA EV HW MN TS Table C4. Configuration Parameters Left Table C4. Configuration Parameters Right DO0 Higher than the value specified for AILowLimit DO4 Seconds = 25.6 seconds DO6PWMPeriod Refer to the description for DO1PWMPeriod Table C5. Direct Access And Special Points Right Table C5. Direct Access And Special Points LeftFig. D-1. Point capacity estimate for Zone Manager Approximate Memory Size Estimating ProcedureResistance Sensors Appendix E. Sensor Data for CalibrationSensor Type Sensor Use1956.79 Voltage/Current Sensors Table E-4. Sensor Voltage Versus HumidityHumidity Percentage Sensor Voltage C7600C1008 4 to 20 mA C7600C output current vs. humidity Sensor Type Fig. E-6. Graph of Sensor Current versus Enthalpy volts Table E-9. Sensor Voltage Versus CO 2 Concentration CO 2 Concentration PPM Sensor VoltageTable E-10. Sensor Voltage Versus Input Voltage To A/D Voltage to A/D Sensor Voltage Table E-11. Sensor Voltage Vdc Versus Pressure InwPressure Inw kPa Sensor Voltage Vdc 3ODD