EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Sensor Type:
T7242 or equivalent.
Sensor Use:
CO2 concentration.
Table
| Table | |
|
|
|
CO2 Concentration PPM | Sensor Voltage |
|
|
|
|
0 | 0.00 |
|
|
|
|
100 | 0.50 |
|
|
|
|
200 | 1.00 |
|
|
|
|
300 | 1.50 |
|
|
|
|
400 | 2.00 |
|
|
|
|
500 | 2.50 |
|
|
|
|
600 | 3.00 |
|
|
|
|
700 | 3.50 |
|
|
|
|
800 | 4.00 |
|
|
|
|
900 | 4.50 |
|
|
|
|
1000 | 5.00 |
|
|
|
|
1100 | 5.50 |
|
|
|
|
1200 | 6.00 |
|
|
|
|
1300 | 6.50 |
|
|
|
|
1400 | 7.00 |
|
|
|
|
1500 | 7.50 |
|
|
|
|
1600 | 8.00 |
|
|
|
|
1700 | 8.50 |
|
|
|
|
1800 | 9.00 |
|
|
|
|
1900 | 9.50 |
|
|
|
|
2000 | 10.00 |
|
|
|
|
SENSOR VOLTAGE VERSUS CO2 CONCENTRATION
VOLTS
10
9
8
7
6
5
4
3
2
1
0
100 | 300 | 500 | 700 |
| 900 | 1100 | 1300 | 1500 | 1700 | 1900 | |||||
200 | 400 |
| 600 | 800 | 1000 | 1200 | 1400 | 1600 | 1800 | 2000 |
PPM | M11611 |
Fig. E-9. Graph of Sensor Voltage versus CO2 concentration.
Sensor Type:
Third party (2 to 20V).
Sensor Use:
Monitor voltage.
Table
Table E-10. Sensor Voltage Versus Input Voltage To A/D.
78 |